5.0 Operation
Charger Standby
appears on LCD.
PWR (green) LED is on solid and CHG
(green) LED blinks. FAULT (red) LED
is off, and INV (green) LED could be
on or off.
FAULT
PWR
CHG
INV
Charger Standby
Settings/Info..
Figure 5-9, Charger Standby Mode
• Charger
Standby
– This means the charger has been disabled to
prevent any charging, but the AC power (from shore/utility or generator)
to the AC input is still available on the AC output. This display is shown
when the ON/OFF CHARGER button is pressed while the AC power is passing
through the inverter/charger.
Info:
To enable charging again, press the ON/OFF CHARGER button.
When the charger is again enabled, the charger will continue in the
Charge mode it last left and the CHG (green) LED will come on solid.
Charging
appears on LCD. PWR
(green) and CHG (green) LEDs are
on solid. FAULT (red) LED is off, and
INV (green) LED could be on or off.
FAULT
PWR
CHG
INV
Charging
Settings/Info..
Figure 5-10, Charging Mode
• Charging
– Once Charging mode has been enabled, the unit will wait and
display “
Charging
” to determine the charge routine. If the DC voltage is low
(
12.8 VDC/12-volt models,
25.6 VDC/24-volt models or
51.2 VDC/48-
volt models), the charger will initiate Bulk Charging. If the DC voltage is
high (>12.8 VDC/12-volt models, >25.6/24-volt models or >51.2/48-volt
models), the charger will skip the Bulk and Absorb charging stages and go
directly to Float Charging.
• Bulk Charging
– The battery charger is delivering maximum current
(determined by the SETUP menu’s
05 Charge Rate
setting) to the batteries.
The charger will remain in Bulk Charge until the absorb voltage (determined
by the SETUP menu’s
04 Battery Type
setting) is achieved.
Bulk Charging
appears on LCD.
PWR (green) is on solid, and CHG
(green) LED is typically on solid, but
may blink. FAULT (red) LED is off. INV
(green) LED could be on or off.
FAULT
PWR
CHG
INV
Bulk Charging
Settings/Info..
Figure 5-8, Bulk Charging Mode