3.0 Setup
Table 3-4, Battery Type to Charge Voltages
Battery
Type
Inverter
Voltage
Absorption
Voltage
Float
Voltage
Equalization
Voltage
GEL
12 VDC
14.1 VDC
13.6 VDC
14.1 VDC
1
24 VDC
28.2 VDC
27.2 VDC
28.2 VDC
1
48 VDC
56.4 VDC
54.4 VDC
56.4 VDC
1
Flooded
12 VDC
14.6 VDC
13.4 VDC
15.5 VDC
24 VDC
29.2 VDC
26.8 VDC
31.0 VDC
48 VDC
58.4 VDC
53.6 VDC
62.0 VDC
AGM 1
2
12 VDC
14.3 VDC
13.1 VDC
15.5 VDC
24 VDC
28.6 VDC
26.2 VDC
31.0 VDC
48 VDC
57.2 VDC
52.4 VDC
62.0 VDC
AGM 2
3
12 VDC
14.5 VDC
13.5 VDC
14.5 VDC
1
24 VDC
29.0 VDC
27.0 VDC
29.0 VDC
1
48 VDC
58.0 VDC
54.0 VDC
58.0 VDC
1
Note
¹
:
Voltage same as absorption voltage—to prevent equalization.
Note
²
:
Charge voltages for Concord (Lifeline Series) AGM batteries.
Note
³
:
Charge voltages for East Penn, Deka, Discover and Trojan AGM batteries.
¸
Battery Type (CC/CV) –
The
CC/CV
selection provides a Constant
Current/Constant Voltage (CC/CV) charging method with an adjustable
charge voltage and a setting that limits output current—if needed. It
consolidates all the battery charge settings that are required for a 2-stage
charging cycle (i.e., Constant Current and Constant Voltage).
Note
:
The CC/CV settings only display if CC/CV has been selected from
the 04 Battery Type menu
.
Info:
If
04 Battery Type
is set to
CC/CV
, the following menus are
no longer accessible and display “
CC/CV Controlled
” when selected:
03 Absorb Time
,
05 Charge Rate
, and
09 Final Charge
. This is to
prevent charging con
fl
icts that could occur while in the CC/CV pro
fi
le.
Max Amps
– Sets the maximum charge amperage allowed to charge
the batteries during the CC/CV charge cycles. The range of settings
are provided to limit the charge current to the battery bank, which
helps prevent battery overheating caused by charging at too high a
charge rate.
Default:
200 ADC
Range:
20 - 990 ADC
Chg Volts
– Sets the voltage level at which the charger will hold
the batteries during the Constant Voltage cycle.
Default:
13.8 VDC (12v), 27.6 VDC (24v), 55.2 VDC (48v)
Range:
OFF, 12.0-16.0 VDC (12v), 24.0-32.0 VDC (24v), 48.0-64.0
VDC (48v)
Info:
The voltage settings shown in Table 3-4 are based on the Bat-
tery Temperature Sensor (BTS) at a temperature of 77° F (25° C),
or not connected. If the BTS is connected, the actual charge voltage
will increase if the temperature around the BTS is below 77° F (25°
C), and decrease if higher than 77° F (25° C). This ensures the bat-