1
© 2016 Sensata Technologies
Introduction
1.0 Introduction
Congratulations on purchasing the ME-AGS-N. This is the ‘network’
version of a Magnum Automatic Generator Start (AGS) controller,
and is set up/operated via a Magnum inverter and remote control
(e.g., ME-RC, ME-ARC, or ME-RTR).
Info: If you need an AGS, but are not using a Magnum inverter/
charger, use the ME-AGS-S (AGS – Standalone).
Using the ME-AGS-N (and depending on your particular remote),
your generator can be set up to automatically start and stop based
on the following conditions:
• Battery
Voltage
– By monitoring battery voltage, the AGS
autostarts the generator when battery voltage falls to a certain
level, and autostops the generator when battery voltage either
rises to a higher level or goes into the Float charge stage—
depending on the remote control.
• Time of Day – Starts/stops the generator daily based on
selected start/stop times (per the remote control’s clock).
• Inverter Load Amps – Starts and stops the generator based
on the loads powered by the inverter (assists with larger loads).
Note: Only applicable to MSH and MS-PAE Series inverters.
• Battery
SOC
– Monitors your battery system and automatically
starts the generator when the battery requires charging—based
on the actual SOC (State of Charge) of the battery.
Note: Battery SOC is a more accurate method than using battery
voltage as a criteria to determine when a battery requires charging.
• Rising
Temperature
– Continuously monitors the temperature
of the surrounding area, and automatically starts the generator
whenever power is needed to run an AC or to cool down an area.
Info: The Battery SOC autostart/autostop feature requires an
installed, optional ME-BMK or ME-BMK-NS (Battery Monitor
Kit) accessory to determine the battery’s SOC.
The AGS-N is also equipped with the following operational features:
• Allows manual on/off control (ME-ARC and ME-RTR only) and
automatic control of the generator
• Compatible with 12, 24, or 48-volt systems
• Adjustable settings made easy using the remote’s AGS menus
(e.g., ME-RC, ME-ARC, or ME-RTR)
• Quiet Time setting prevents generator operation at night
• TEST button that con
¿
rms if installation wiring is correct
• Removable 8-port terminal block for easy wiring/powering down
• Front panel LED indicators for gen start/stop status and faults