11
51-638 Echotel Model 338 Two-Wire Ultrasonic Transmitter
NOTE: Tank or flume/weir dimensions must be entered prior to dis-
playing volume or open channel flow values. Programming for
these parameters begins with
P40.
b
Bar Graph Indication
0
Echo strength
1
Current output
a
Measurement Mode
Displayed Measurements
0
Distance
DIST
1
Level
LEV, DIST
2
Level in percentage
LEV%, LEV, DIST
3
Volume
VOL, LEV, DIST
4
Volume in percentage
VOL%, VOL, LEV, DIST
5
Flow
FLOW, T1, T2, LEV, DIST
P02: - cba
Calculation Units
Factory default value for P02 is: 000
Engineering units for volume are selected in "b", and units
for open channel flow are selected using "b" and "c".
Metric or US for "b" is selected by the value of "c" in P00.
The volume can also be displayed in units of weight by
setting "b" and entering the density of the fluid in P32.
The value of "a" determines the temperature units when
the UP
key is pressed in the operating mode.
b
Volume
Weight (set also P32) Open Channel Flow
US
Metric
US
Metric
US
Metric
0
ft
3
m
3
lbs (pounds)
–
ft
3
/time
m
3
/time
1
gallons
liter
tons
tons
gallons/time liter/time
c
Time
0
Sec
1
Min
2
Hour
3
Day
a
Temperature
0
° C
1
° F
P01: - ba
Bar Graph and Measurement Mode
Factory default value for P01 is: 11