51-638 Echotel Model 338 Two-Wire Ultrasonic Transmitter
1.5.3 Basic Functions
The commands below set the basic functions of the 338
transmitter during
QuickSet Configuration.
Shown below are some additional commands that can
be used while in the
QuickSet
menu. The "Get Level"
command is especially useful if the level or distance is
unknown, and the liquid is at the proper height in
the tank.
1.5.4 Setting
QuickSet Configuration
Parameters
The table on page 8 shows how to set all six of the
QuickSet Configuration
parameters.
NOTE: Current output can also be programmed for inverted
operation: 4 mA = 100% (Full), 20 mA = 0% (Empty)
NOTE: If a parameter value is not accepted by the LCD module, the
existing parameter value will keep blinking. This is due to:
1. The value is out of range (example would be trying to
enter a range value larger than 20.00 feet)
2. The parameter value is not valid for this screen
Pushbutton Keys
Function
ENTER
+ DOWN
Enter or exit
QuickSet Configuration
(press for 3 seconds)
menu
UP
or DOWN
Increase or decrease value of blinking
digit, or scroll up/down to change
parameters
NEXT
Move the blinking digit to the left
(to change its value)
ENTER
Saves the value currently being dis-
played and moves to the next
QuickSet
parameter
Pushbutton Keys
Function
UP
+ DOWN
Accesses the "Get Level" screen to
(press for 3 seconds)
display the actual measured level or
distance currently being measured by
the Model 338 transmitter
NEXT
+ UP
Reset parameter back to the previously
saved value
NEXT
+ DOWN
Reset the currently displayed parameter
back to the factory default value
LEV