57-657 SIL Certified Safety Manual for ECLIPSE Model 706

1.0

Introduction

1.1

Product Description

The ECLIPSE Model 706 High Performance Guided Wave
Radar Level Transmitter is a two-wire, loop-powered
24 VDC level transmitter based on Guided Wave Radar
(GWR) technology.

NOTE: For Safety Instrumented Systems usage, it is assumed that the

4–20 mA output is used as the safety variable.

The analog output from the Model 706 meets the NAMUR
NE 43 standard (3.8 mA to 20.5 mA usable). The transmitter
contains self-diagnostics and is programmed to drive the
output to a user-selected failure state, either low or high,
upon internal detection of a diagnostic indicator. The device
can be equipped with or without an optional non-interfering
graphic liquid crystal display (LCD).

Table 1 indicates the version of the ECLIPSE Model 706
transmitter that has been certified for SIL 2/3 applications.

1.2

Theory of Operation

Guided Wave Radar is based upon the principle of TDR
(Time Domain Reflectometry). TDR utilizes pulses of electro-
magnetic energy transmitted down a wave guide (probe).
When a pulse reaches a liquid surface that has a higher
dielectric constant than the air (

ε

r

= 1) in which it is traveling,

a portion of the pulse is reflected. The transit time of the
pulse is then measured via ultra high-speed timing circuitry
that provides an accurate measure of the liquid level. The
amplitude of the reflection depends on the dielectric con-
stant of the product. The higher the dielectric constant, the
larger the reflection.

1.3

Determining Safety Integrity Level (SIL)

Safety Instrumented System designers using the Enhanced
ECLIPSE Model 706 must verify their design per applicable
standards, including IEC 61511-1.

Three limits must be met to achieve a given SIL level:

1. The PFD

AVG

numbers for the entire Safety Instrumented

Function (SIF) must be calculated. Table 2 shows the rela-
tionship between the Safety Integrity Level (SIL) and the
Probability of Failure on Demand Average (PFD

AVG

).

2. Architecture constraints must be met for each subsystem.

Table 3 can be used to determine the achievable SIL as a
function of the Hardware Fault Tolerance (HFT) and the 

Table 3

Minimum hardware fault tolerance

Type B sensors, final elements and non-PE logic solvers

SFF

Hardware Fault

Tolerance (HFT)

0

1

2

None: <60%

Not

Allowed

SIL 1

SIL 2

Low:

60% to <90%

SIL 1

SIL 2

SIL 3

Medium: 90% to <99%

SIL 2

SIL 3

High:

99%

SIL 3

Table 2

SIL vs. PFDavg

Safety

Integrity Level

(SIL)

Target Average

probability of failure

on demand (PFDavg)

4

10

-5

to <10

-4

3

10

-4

to <10

-3

2

10

-3

to <10

-2

1

10

-2

to <10

-1

1

Transmitters:

Model 706, 706-512*-*** (HART)

Hardware Version (or later)

Analog Board 030-9160-001 Rev K
Digital Board 030-9159-001 Rev AC
Wiring Board 030-9165-001 Rev F

Software Version (or later)

Model 706 HT 1.0hA.hex

2

Probes:

All ECLIPSE probes can be utilized.
Refer to I/O Manual 57-606 for
complete probe offering.

Table 1
Enhanced ECLIPSE Model Numbers

Содержание ECLIPSE 706 Series

Страница 1: ...n the output will be driven to the customer specified out of range signal i e 3 6 mA or 21 mA The Enhanced Model 706 is certified for use in low demand level measurement applications Application The H...

Страница 2: ...ronmental 6 6 1 2 1 Operating 6 6 1 2 2 Storage 6 6 2 Installation 6 6 3 Skill Level of Personnel 6 6 4 Necessary Tools 7 6 5 Configuration Information 7 6 5 1 General 7 6 5 2 Configuration 7 6 5 3 Wr...

Страница 3: ...the liquid level The amplitude of the reflection depends on the dielectric con stant of the product The higher the dielectric constant the larger the reflection 1 3 Determining Safety Integrity Level...

Страница 4: ...Serial Number shown on the name plates 3 0 Level Measuring System The diagram at left shows the structure of a typical measuring system incorporating the ECLIPSE Model 706 transmitter This SIL 2 3 Ce...

Страница 5: ...an Time To Repair MTTR SIL determinations are based on a number of factors including the Mean Time To Repair MTTR The analysis for the ECLIPSE Model 706 is based on a MTTR of 24 hours 5 0 Supplementar...

Страница 6: ...Manual 57 606 for Environmental limitations 6 1 2 1 Operating The operating temperature range is 40 to 175 F 40 to 80 C 6 1 2 2 Storage The device should be stored in its original shipping box and not...

Страница 7: ...nfiguration Ensure the Model 706 transmitter has been properly config ured for the application and probe Special consideration should be given to the following configuration parameters Dielectric Rang...

Страница 8: ...nse Times Continuous internal diagnostics are present within the Enhanced ECLIPSE Model 706 transmitter In the event a Fault is detected a message will appear on the LCD and the output current will be...

Страница 9: ...indicate OK b Choose the menu DIAGNOSTICS EVENT HISTORY Event Log i Any FAULT or WARNING messages must be investigated and understood ii Corrective actions should be taken for FAULT messages continued...

Страница 10: ...curves a Select DIAGNOSTICS ECHO CURVE View Echo Curve i Observe the present Echo Curve identify the characteristic portions of the waveform related to the FIDUCIAL Process level End of Probe and othe...

Страница 11: ...figuration parameters avail able via the Local User Interface during normal operation The end user will enable the User Password to lock out any end user modifiable configuration parameters avail able...

Страница 12: ...will respond to a change from the user s process within the safety function response time The Eclipse Model 706 shall transition to the Faulted Mode from the Normal Mode within the Diagnostic Test Int...

Страница 13: ...13 57 657 SIL Certified Safety Manual for ECLIPSE Model 706 9 0 Appendices 9 1 SIL Certificate...

Страница 14: ...14 57 657 SIL Certified Safety Manual for ECLIPSE Model 706 9 2 FMEDA Report exida Management Summary...

Страница 15: ...itself and its operating conditions The assumption of a constant failure rate is based on the bathtub curve Therefore it is obvious that the PFDavg calculation is only valid for components that have...

Страница 16: ...Mod Guideline on the Implementation of ANSI ISA 84 00 01 2004 Service Policy Owners of MAGNETROL controls may request the return of a control or any part of a control for complete rebuilding or replac...

Отзывы: