10
Control unit MGC
Digital inputs, digital outputs and relay outputs
2
Digital inputs, digital outputs and relay outputs
WARNING
Improper wiring and parameterisation of the control unit!
Improper wiring and parameterisation of the control unit can
lead to undesired functions and thus to injuries.
›
Only MHTM™ FlowMotion® service experts or skilled
technicians or electrical safety experts may wire up and
parameterise the control unit.
›
The electrical connection of the signal transmitters to the IN1
to IN8 inputs must fit the parameterisation.
Parameterisation:
2.1
Digital inputs
Definition of "Left" and "Right":
By parameterising the inputs, you assign certain functions to the inputs. For
example, if you parameterise the "Illumination off" function for input IN7, you
must connect a illumination to this input.
If the function is marked with "|", the input is inverted (Fail Safe).
The following functions are assigned to the inputs as default settings:
Clamp
Description
Function
IN1
Digital input 1
| Emergency open
IN2
Digital input 2
Open from left
IN3
Digital input 3
Open from right
IN4
Digital input 4
–
IN5
Digital input 5
Confirm warnings
IN6
Digital input 6
Close (Inhibit opening)
IN7
Digital input 7
Illumination off
IN8
Digital input 8
–
Table 3:
Factory settings "Digital inputs"