background image

 Technical Service Manual

MKG Series Gas Griddles

L22-296 Rev 0 (4/08)

Page 9

Photo 14

Photo 15

Photo 16

Photo 17

4.2 

PILOT / IGNITION SYSTEM CHECK

4.2.1 

Ignitor Check- Snap Action Series

 

Verify actuation of Piezo ignitor by depressing
red button on front panel, (A in Photo 1). A loud
“click” or “snap” sound should be detected.

 

Verify both terminal connections of the ignition
wire, (A, in Photo 10), and check the wire for
visible damage and electrical continuity.

Note: Front panel must be “grounded” to the

appliance to establish sufficient spark

 

Check to ensure that the Piezo ignitor, (B, in
Photo 10). is tightly mounted to the panel. A
loose connection may create an open “ground”.

 

Inspect the electrode(B), and the ceramic
insulator(E) for visible damage, See Photo 14.

 

Verify the spark gap between the electrode(B),
and the pilot hood(A), nominal gap is .090”.

 

If all parts are in good condition, check for

sufficient spark by first removing the ignition
wire,(C) from the electrode terminal.

 

Hold the “open” terminal of the ignition wire 1/8”
from front panel with insulated pliers, and
depress the red button of the Piezo ignitor.
Check for a visible spark to the panel, See
Photo 15.

 

If no spark is produced, replacement of the
Piezo ignitor may be required.

 

To Replace remove the ignition wire from the
ignitor and save. Remove the ignitor from the
panel by removing retaining nut located on the
back of the panel.

 

Install new Piezo ignitor in reverse order,
making sure to replace all hardware, and
insure all wires and gas tubing are re-
connected to original condition.

4.2.2 

Spark Failure- Matchless (E & ST)
Series

 

Turn on power switch, look and listen for a
steady arc from the pilot assembly. An
unstable arc may be caused by spark leakage,
or an insufficient gas supply to the pilot.

 

Spark leakage can be due to an excessive
spark gap between the pilot(A), and the
electrode(B), nominal gap is .125”. Damaged
parts, or a loose Ignition wire(C), may result in

spark leakage also, See Photo 16.

 

Inspect all parts and wiring connections and
repair or replace as necessary.

 

An insufficient gas supply to the pilot can be
caused by a dirty or clogged pilot orifice(D), or
low gas pressure at the supply regulator.

 

Disconnect pilot tubing from pilot to access the
pilot orifice(D), clean or replace as needed.

Содержание MKG24

Страница 1: ...ual for the life of the equipment Model ___________________________ Serial ___________________________ Date Purchased ____________________ ENGLISH Models MKG24 MKG36 MKG48 MKG60 MKG72 All Options Buil...

Страница 2: ...k disconnect must comply with ANSI Z24 41 WARNING DO NOT alter or remove structural material on the appliance to accommodate placement under a ventilation hood WARNING This appliance is intended for p...

Страница 3: ...4 2 3 Insufficient or Absence of Flame 10 4 2 4 Pilot Lock in Snap Action Series 10 4 2 5 Pilot Lock in Matchless Series E ST 10 4 3 IGNITION MODULE REPLACEMENT 10 4 4 PILOT ASSEMBLY REPLACEMENT 11 4...

Страница 4: ...ns and grease chute options Suffix E models have flame proving spark ignition systems and electro mechanical thermostats External power supply is required Suffix ST models have flame proving spark ign...

Страница 5: ...C and controlled by the gas regulator D mounted in the back of the unit See Photo 1a 2 2 HEATING SYSTEM MATCHLESS IGNITION SERIES E ST Start up of Unit See Photo s 2 and 2a Open the shut off valve C P...

Страница 6: ...inserted into a hole at the end of the slot 3 Temperature Calibration Each temperature control operates a twelve 12 inch zone Each zone consists of two burners except for zones containing a left or r...

Страница 7: ...e the knob Once the retaining nut is loose pull straight out on the knob to insure that the knob can move freely on the shaft Align the white indicator line with the average temperature of the corresp...

Страница 8: ...mpartment See Photo 12 Pull lower panel away from front of appliance this will give access to the gas valves ignition modules and temperature controls To remove the upper switch panel remove the 10 se...

Страница 9: ...el with insulated pliers and depress the red button of the Piezo ignitor Check for a visible spark to the panel See Photo 15 If no spark is produced replacement of the Piezo ignitor may be required To...

Страница 10: ...o 41 from the safety valve and measure the output between the contact and ground Open circuit output should be greater than 15mv closed circuit should be greater than 8mv thermocouple connected Note T...

Страница 11: ...ter B opening can cause incomplete combustion or yellow flames at the burner ports See Photo 22 To align the burner manifold D loosen or tighten manifold Bracket screws E until the manifold orifices a...

Страница 12: ...ke care to not damage the brass fittings or pipe threads See Photo 24 Prior to installing the new orifices insure that the fittings are not clogged and reapply thread sealant to all male threads where...

Страница 13: ...ain that the end of the burner B is located on the indexing pin A of the burner mounting plate See Photo 28 Re install the remaining screws runner tube and sheet metal in reverse order Insure that all...

Страница 14: ...d operation of the contacts as follows Remove lower front panel refer to Section 4 1 2 Light pilots refer to Section 2 2 when pilots are lit turn all thermostats to the Off position Using a voltmeter...

Страница 15: ...ove wire connections E from the Solid State temperature control See Photo 33 Using a multi meter check the probe resistance against the cooking surface temperature Use the Resistance Chart in Section...

Страница 16: ...wire terminals B C from the thermostat with needle nose pliers or other adequate tool Photo 31 Pull the thermostat knob off the thermostat shaft Remove the thermostat from the mounting bracket by rem...

Страница 17: ...1 SAFETY VALVE REPLACEMENT Snap Action Models If the test criteria from Section 4 2 4 have been met but the appliance does not operate properly replacement of the Safety valve may be required Shut off...

Страница 18: ...mounting screw s that secure the assembly to the framework of the cabinet There is one screw above and below the solenoids See Photo 44 Disconnect all piping and fittings from the inlet A and outlet...

Страница 19: ...2 Faulty gas connection 3 Manual shut off closed 4 Defective Safety valve 1 Check that all gas connections are turned On verify gas pressure at the regulator 2 Verify that all connections are fully En...

Страница 20: ...ify internal ground connection Replace power cord if ungrounded Pilot will not stop sparking 1 No gas to pilot burner 2 Spark gap incorrect 3 Spark leakage 4 Un grounded power cord 1 Check pilot solen...

Страница 21: ...ON OFF RIGHT MODULE IGNITION ORG L1 K1 IM1 K3 J P1 3 ORG S1B MAIN VALVE J P1 5 W RED BGND HV GRN Y MV1 RIGHT PILOT VALVE PV1 L2 V2 L2 YEL WHT PV1 115V 50 60Hz NEMA 5 15P PP10439 BRN 4A BLK 3 PILOT OK...

Страница 22: ...HEAT CONTROL TEMP TC1 5 4 NO 7 COM 6 S2B TP2 WHT R 3 MV1 J P1 1 VIOL ORG 4 5 ON OFF RIGHT MODULE IGNITION TP1 ORG L1 K1 IM1 K3 J P1 3 ORG S1B MAIN VALVE J P1 5 W RED BGND HV GRN Y MV1 RIGHT PILOT VAL...

Страница 23: ...VIOL VIOL J P1 5 WHT BLU S1 4 5 BRN J P4 1 BLU MODULE J P1 1 IGNITION IM1 W RED WHT MAIN VALVE MV1 RIGHT GRN Y PILOT VALVE J P1 4 WHT L2 V2 L2 ON OFF R 3 BLU WHT TC1 CONTROL TEMP K3 L1 MV1 HEAT ORG G...

Страница 24: ...L NEXT PAIR BGND HV ORG BLU TC2 TEMP CONTROL J P4 6 HEAT VIOL VIOL J P1 5 WHT BLU S1 4 5 BRN J P4 1 BLU MODULE J P1 1 IGNITION IM1 W RED WHT MAIN VALVE MV1 RIGHT GRN Y PILOT VALVE J P1 4 WHT L2 V2 L2...

Страница 25: ...Trouble Shooting Guide MKG Series Gas Griddles L22 296 Rev 0 4 08 Page 25 Notes...

Страница 26: ...684 World Wide Website Address www magikitchn com In the event of problems with or questions about your equipment please contact the MagiKitch n Authorized Service and Parts representative ASAP coveri...

Отзывы: