Magikitch'n MKG24 Скачать руководство пользователя страница 10

Technical Service Manual
MKG Series Gas Griddles

Page 10

L22-296 Rev 0 (4/08)

Photo 18

 

If no spark is evident, check for 115 VAC to the
ignition module between terminal L1 and
chassis ground, also verify all other ground
connections, See Photo 17.

 

If 115 VAC 

IS NOT

 present at the ignition

module, check that the external power cord is
plugged in to live 115V outlet, and the fuse in
the yellow fuse holder (C) is good.

 

If 115 VAC 

IS

 present at the ignition module,

but no spark generated, replace the ignition
module, See Section 4.3.

4.2.3 

Insufficient or Absence of Flame:

 

An insufficient pilot flame can result in a loss of
flame sense to the ignition module on a
Matchless ignition appliance, or loss of
sufficient millivoltage to actuate a Snap Action
appliance.

 

The tips of the pilot flame originating from the
pilot hood(A), should visibly extend above each
pilot runner tube(B). If flame is not visible, the
ignition system may fail to activate the main
burner system See Photo 18.

 

Common causes of insufficient pilot flame are

NO, 

or 

LOW

 gas supply pressure, a pilot orifice

that has become clogged with foreign debris.

 

Verify gas pressure at the manual shut off

valves, (C), in Photo 1 for Snap Action models,
and (C), in Photo 2a for Matchless Ignition
models. The table in Section. 1.3.1 has the
nominal gas pressure for each gas type.

 

Pilot orifices can be checked by disconnecting
the ¼” tubing from the pilot assembly, (D, in
Photo 14 for Snap Action, and D, in Photo 16,
for Matchless Ignition models. Refer to section
4.4 for pilot removal from the appliance.

 

The gas flow to the pilot can be checked by
connecting a manometer to the disconnected
¼” tubing going to the pilot. Refer to Section 2
for each model to initiate gas flow to the pilot.

4.2.4 

Pilot Lock-in: Snap Action Series

If a sufficient pilot flame is present, but the
main valve will not engage, check the millivolt
output of the thermocouple (F, in Photo 14) .
Disconnect the thermocouple contact (D, in
Photo 41) from the safety valve and measure
the output between the contact and ground.
Open circuit output should be greater than
15mv. closed circuit should be greater than
8mv (thermocouple connected).

Note

: To measure a closed circuit use of a

thermocouple test adapter. The thermocouple
contact must not be cross threaded, and must
be tightened to1/4-1/2 turn past finger tight.

 

If the millivolt output does not meet the
minimum voltage, replace thermocouple.

 

If the thermocouple is properly connected, and
the millivolt output is sufficient (25-35mV, No
Load), but safety valve will not engage,
replace the safety valve, see section 4.11.

 

If pilot flame and millivolt readings are normal
but there is no flame at the main burner, check
thermostat operation, refer to section 4.9.1.

4.2.5 

Pilot Lock-in- Matchless Series (E & ST)

 

The electronic ignition system is an integral
flame sense system. This means that the
module supplies spark, and senses flame
current with the same electrode. The pilot
assembly, ignition module, and the appliance
must be properly grounded to operate
properly.

 

The ignition module is grounded to the chassis
directly at the pilot bracket (A, in Photo 20)

.

The appliance is equipped with a NEMA 5-15
grounded plug, extension cords are not
recommended for use with the appliance.

 

When properly grounded, and adequate pilot
flame are established as described in section
4.2.2, but spark continues for 90 seconds
followed by an ignition module lock out, there
is a flame sense failure. Replace the ignition
module as described in section 4.3.

4.3 

IGNITION MODULE REPLACEMENT

 

The ignition modules are mounted in the unit,
but the replacement procedure is identical for
all ignition modules, See Photo 19.

 

Remove the two- (2) screws(A) holding the
ignition module mounting plate in place.

 

Remove module from mounting plate.

 

Disconnect ignition wire(B), and control
wiring(C) by carefully pulling upward on the
wire terminals with electrical pliers. To rewire
the ignition module correctly, it is advised to
label the wires. Miswiring the ignition module
may result in injury, or damage the appliance.

 

Mount the new module to the mounting plate.

 

Remount the assembly.

8

Содержание MKG24

Страница 1: ...ual for the life of the equipment Model ___________________________ Serial ___________________________ Date Purchased ____________________ ENGLISH Models MKG24 MKG36 MKG48 MKG60 MKG72 All Options Buil...

Страница 2: ...k disconnect must comply with ANSI Z24 41 WARNING DO NOT alter or remove structural material on the appliance to accommodate placement under a ventilation hood WARNING This appliance is intended for p...

Страница 3: ...4 2 3 Insufficient or Absence of Flame 10 4 2 4 Pilot Lock in Snap Action Series 10 4 2 5 Pilot Lock in Matchless Series E ST 10 4 3 IGNITION MODULE REPLACEMENT 10 4 4 PILOT ASSEMBLY REPLACEMENT 11 4...

Страница 4: ...ns and grease chute options Suffix E models have flame proving spark ignition systems and electro mechanical thermostats External power supply is required Suffix ST models have flame proving spark ign...

Страница 5: ...C and controlled by the gas regulator D mounted in the back of the unit See Photo 1a 2 2 HEATING SYSTEM MATCHLESS IGNITION SERIES E ST Start up of Unit See Photo s 2 and 2a Open the shut off valve C P...

Страница 6: ...inserted into a hole at the end of the slot 3 Temperature Calibration Each temperature control operates a twelve 12 inch zone Each zone consists of two burners except for zones containing a left or r...

Страница 7: ...e the knob Once the retaining nut is loose pull straight out on the knob to insure that the knob can move freely on the shaft Align the white indicator line with the average temperature of the corresp...

Страница 8: ...mpartment See Photo 12 Pull lower panel away from front of appliance this will give access to the gas valves ignition modules and temperature controls To remove the upper switch panel remove the 10 se...

Страница 9: ...el with insulated pliers and depress the red button of the Piezo ignitor Check for a visible spark to the panel See Photo 15 If no spark is produced replacement of the Piezo ignitor may be required To...

Страница 10: ...o 41 from the safety valve and measure the output between the contact and ground Open circuit output should be greater than 15mv closed circuit should be greater than 8mv thermocouple connected Note T...

Страница 11: ...ter B opening can cause incomplete combustion or yellow flames at the burner ports See Photo 22 To align the burner manifold D loosen or tighten manifold Bracket screws E until the manifold orifices a...

Страница 12: ...ke care to not damage the brass fittings or pipe threads See Photo 24 Prior to installing the new orifices insure that the fittings are not clogged and reapply thread sealant to all male threads where...

Страница 13: ...ain that the end of the burner B is located on the indexing pin A of the burner mounting plate See Photo 28 Re install the remaining screws runner tube and sheet metal in reverse order Insure that all...

Страница 14: ...d operation of the contacts as follows Remove lower front panel refer to Section 4 1 2 Light pilots refer to Section 2 2 when pilots are lit turn all thermostats to the Off position Using a voltmeter...

Страница 15: ...ove wire connections E from the Solid State temperature control See Photo 33 Using a multi meter check the probe resistance against the cooking surface temperature Use the Resistance Chart in Section...

Страница 16: ...wire terminals B C from the thermostat with needle nose pliers or other adequate tool Photo 31 Pull the thermostat knob off the thermostat shaft Remove the thermostat from the mounting bracket by rem...

Страница 17: ...1 SAFETY VALVE REPLACEMENT Snap Action Models If the test criteria from Section 4 2 4 have been met but the appliance does not operate properly replacement of the Safety valve may be required Shut off...

Страница 18: ...mounting screw s that secure the assembly to the framework of the cabinet There is one screw above and below the solenoids See Photo 44 Disconnect all piping and fittings from the inlet A and outlet...

Страница 19: ...2 Faulty gas connection 3 Manual shut off closed 4 Defective Safety valve 1 Check that all gas connections are turned On verify gas pressure at the regulator 2 Verify that all connections are fully En...

Страница 20: ...ify internal ground connection Replace power cord if ungrounded Pilot will not stop sparking 1 No gas to pilot burner 2 Spark gap incorrect 3 Spark leakage 4 Un grounded power cord 1 Check pilot solen...

Страница 21: ...ON OFF RIGHT MODULE IGNITION ORG L1 K1 IM1 K3 J P1 3 ORG S1B MAIN VALVE J P1 5 W RED BGND HV GRN Y MV1 RIGHT PILOT VALVE PV1 L2 V2 L2 YEL WHT PV1 115V 50 60Hz NEMA 5 15P PP10439 BRN 4A BLK 3 PILOT OK...

Страница 22: ...HEAT CONTROL TEMP TC1 5 4 NO 7 COM 6 S2B TP2 WHT R 3 MV1 J P1 1 VIOL ORG 4 5 ON OFF RIGHT MODULE IGNITION TP1 ORG L1 K1 IM1 K3 J P1 3 ORG S1B MAIN VALVE J P1 5 W RED BGND HV GRN Y MV1 RIGHT PILOT VAL...

Страница 23: ...VIOL VIOL J P1 5 WHT BLU S1 4 5 BRN J P4 1 BLU MODULE J P1 1 IGNITION IM1 W RED WHT MAIN VALVE MV1 RIGHT GRN Y PILOT VALVE J P1 4 WHT L2 V2 L2 ON OFF R 3 BLU WHT TC1 CONTROL TEMP K3 L1 MV1 HEAT ORG G...

Страница 24: ...L NEXT PAIR BGND HV ORG BLU TC2 TEMP CONTROL J P4 6 HEAT VIOL VIOL J P1 5 WHT BLU S1 4 5 BRN J P4 1 BLU MODULE J P1 1 IGNITION IM1 W RED WHT MAIN VALVE MV1 RIGHT GRN Y PILOT VALVE J P1 4 WHT L2 V2 L2...

Страница 25: ...Trouble Shooting Guide MKG Series Gas Griddles L22 296 Rev 0 4 08 Page 25 Notes...

Страница 26: ...684 World Wide Website Address www magikitchn com In the event of problems with or questions about your equipment please contact the MagiKitch n Authorized Service and Parts representative ASAP coveri...

Отзывы: