Page 3
1.1 Ventilation Requirements
1. For models with heat inputs not exceeding 6.9kW additional ventilation is not normally
required in the room that the fire is fitted. However, if spillage is detected during spillage
test additional ventilation may be required. In GB reference should be made to BS
5871:Part 3, and in IE, reference should be made to the current edition of I.S.813 which
makes clear the conditions that must be met to demonstrate that sufficient ventilation is
available.
2. Models with heat inputs in excess of 6.9kW require a minimum of 100cm
2
ventilation in the
room where the fire is installed when installed in Great Britain (GB) and in IE, reference
should be made to the current edition of I.S.813 which makes clear the conditions that
must be met to demonstrate that sufficient ventilation is available.
3. If provided, any purpose provided ventilation must be checked periodically to ensure it is
free from obstructions.
4. When fitting the fire in Northern Ireland (NI), purpose provided ventilation must be
provided in accordance with the rules in force.
5. In other EC countries equivalent rules in force must be used.
Flue Requirements
This fire is suitable for installation using a flue system with a minimum cross sectional area
equivalent to a 175mm (7”) diameter flue e.g. Masonry chimney. However, should the
model being installed have a heat input of 6.9kW then the flue requirements as set out in
SECTION
0
may be applicable. Please refer to the full Flue and Chimney Requirements
within the Installation Instruction section.
Gas Supply
1. This decorative gas fire is suitable for use with either Natural Gas (G20) at 20mbar supply
pressure or with Propane (G31) at 37mbar supply pressure.
2. A separate means of isolating the gas supply should be provided near to the appliance to
facilitate servicing. For this an isolating valve has been supplied.
Electrical Supply
Not applicable to this range of appliances.
1.2 Important Note About ODS Pilot
This fire is fitted with an ODS pilot which causes the appliance to shut down in the event of a
reduction of oxygen (e.g. caused by poor ventilation) in the room. Should this happen, follow
the lighting instructions to re-light the fire. In the event that the fire should shut down again,
do NOT attempt to re-light it but contact your gas installer for remedial action to be taken.
Under no circumstances should it be adjusted or put out of action by the installer
or the user. In case the pilot needs replacing, only the approved part (available
from your supplier or Burley Magiglo.) should be fitted. Note: if any part of the
pilot assembly becomes faulty the complete assembly will need replacing.