3.9.9. Checking for Spillage
1. Close all doors and windows.
2. Turn the fire on to its maximum setting
and leave it burning for 5 minutes.
3. Test for spillage using a smoke match (in
a ‘Blume tube’) at the top of the
appliance opening at the centre, with the
smoke match being approximately 6 -
12mm (¼ - ½ inches) inside and 25mm
under the canopy. If the test indicates
spillage, repeat the test after a further 10
minutes.
4. If there are any extractor fans in nearby
rooms then repeat the smoke match test
with all these fans operating and any
interconnecting doors open between the
fans and the fire.
5. If the fire shows tendency to spill, this
may indicate either an installation fault or
a flue construction fault.
Disconnect
the fire and seek expert advice.
The imitation fuels must be laid
in accordance with the
instructions prior to
commencing the spillage test.
Smoke match applied
6 - 12mm inside and
25mm under the canopy.
Figure 60
3.9.10. 49BInstructing the User
The installer must hand over these
instructions to the user and explain how to
operate this fire, stressing the importance of
having the fire checked and serviced
regularly. An annual service is
recommended.
It is mandatory as part of the
gas installation that the installer
instructs the user on the correct
operation and care of their
appliance.