Page 35
3.9.8. Commissioning
1. Turn on the gas supply to the fire and
purge the gas line. Check all the gas
joints for gas soundness.
2. Connect a pressure gauge to the
pressure test point on the isolating valve
on the appliance.
3. Ignite the pilot in accordance with the
User Instructions.
4. Set the controls to give full gas rate at
the main burner.
5. Ensure that the inlet pressure at the
pressure test point is 20 +1.0mbar for
Natural Gas or 37 +1.0mbar for Propane
(working pressure)
6. If the correct pressure cannot be
achieved, then some potential causes of
low pressure are:
a) Supply pipes are not of large enough
diameter.
b) The supply pipes are kinked, blocked
or partially blocked.
c) Restriction at the appliance isolation
valve.
7. Set the controls to the low rate position
(small flame position) and check that the
fire goes to its low setting.
8. Turn the fire off.
9. Lay the coals or pebbles in accordance
with the instructions in the Users Section
of this booklet.
10. Proceed to carry out a spillage test.