background image

 

 

 

16.

 

Boiler Installation 

 
Boilers  are  typically  supplied  to  customers  equipped  with  basic  boiler  regulation.  The  regulation  ensures  the  required  heating 
water output temperature of 75 to 90° C. It does not cover the control of mixing valves and pumps. Each of the pumps within the 
system  must  be  operated  by  a  separate,  independent  thermostat  in  order  that  the  reverse  operation  is  not  overcooled  (i.e.  the 
reverse  temperature  should  not  drop  below  60°C).  If  a  boiler  is  installed  without  a  heat  storage  unit  or  without  an  equalizing 
reservoir, any pump located within the heated spaces must be operated (switched on and off) by an independent thermostat or b y 
means  of  electronic  regulation  so  that  such  pump  only  runs  when  the  boiler  circuit’s  pump  is  running.    If  you  use  two 
thermostats (each of them to operate a single pump), then you should set the boiler pump’s switch-on temperature to 75 °C and 
the switch-on temperature for the heating circuit’s pump to 80 °C. At least one pump need to be equipped with filter.          
 
The selection of the required temperature for the water running into the heated building (spaces) is done using a 3-way of 4-way 
mixing  valve.  The  3-way  valve  itself  does  not  provide  boiler’s  only-hot-water  security.    Such  mixing  valve  can  either  be 
operated manually or through an electronic regulating device that will provide a more comfortable and more economic operation 
of  the  boiler.  Any  related  electrical  wiring  and  devices  must  be  done/installed  by  authorized  professional  personnel  in 
accordance with the STN EN standard. 
 

Protecting your boiler from low-temperature corrosion. 

 

 

The  boiler  is  required  to  be  installed/connected  with  a  Laddomat  or  thermoregulating  valve.  This  way  of  connection 
provides the thermal separation of the boiler and the heating circuits so that it can ensure a minimum temperature of 60 
°C  for  the  return  water  running  back  to  the  boiler.    The  output  water  temperature  must  be  kept  constant  within  the 
range from 75 to 90 °C.  Under normal operating conditions, the temperature of the combustion products must never fall 
below  the  minimum  of  110 °C.    A  low  temperature  of  the  combustion  products  results  in  the  condensation  of  tars  and 
acids although the output water temperature is kept within the range of 75  - 90 °C and the return water temperature is 
kept  at  60  degrees  centigrade.    Such  conditions  may  occur,  for  instance,  during  the  heating  of  hot  tap  water  in  the 
summer  seasons  or  when  only  a  portion  of  a  building  is  being  heated.  In  such  cases  we  recommend  that  the  boiler  be 
connected with heat storage units (tanks) or lighting the boiler on a daily basis. The boiler must not be operating for a 
long time period below 60% of its maximum output capacity.     

 

 

 

 

Boiler Installation/Connection with Laddomat 

 
 
 
 

Содержание MA 15

Страница 1: ...MA 31 MA 40 MA 49 MA 80 With an exhaust fan and CONTROL UNIT ERS AK 6000 BOILER OPERATION AND MAINTENANCE MANUAL MAGA s r o S Koll ra 86 979 01 eren any Rimavsk Sobota Slovakia Tel fax 421 47 56 34 79...

Страница 2: ...and a minimum return water temperature of 60 C 140 F The pump must be connected to the thermo switch in such a way that it only operates when the required minimum temperature is reached 4 The boiler m...

Страница 3: ...25 0 25 Boiler Weight kg 310 350 380 Exhaust Socket Diameter mm 159 159 159 Boiler Height mm 1120 1120 1210 Boiler Depth mm 1000 1140 1140 Boiler Width mm 570 570 570 Water capacity l 65 70 75 Boiler...

Страница 4: ...red boiler must be operated in accordance with the instructions contained in this operating and maintenance manual The boiler must be operated by adults only CAUTION When you fire up a new boiler for...

Страница 5: ...y For the boilers MA approximate dimensions of the boiler s cross section are 20 x 20 cm Minimum height 7 m 20 cm Minimum height 8m Exact dimensions of a chimney for this purpose in Slovakia are gover...

Страница 6: ...al s such floor must be shielded with a thermally insulating fireproof board extending at least 300 mm beyond the ground plan on the firetending side and at least 100 mm beyond the ground plan on all...

Страница 7: ...nce to a boiler that is currently under operation When operating a solid fuel fired boiler no inflammable liquids are permitted to be used for firing up Increasing in any manner a boiler s output capa...

Страница 8: ...et 9 Primary air inlet 10 Ceramics nozzle 11 Firing flap valve 12 Primary air inlet duct 13 Clean out cover 14 Smoke flue outlet 15 Firing valve s draw rod 16 Fuse 17 Chimney sensor flue gas temperatu...

Страница 9: ...lly or through an electronic regulating device that will provide a more comfortable and more economic operation of the boiler Any related electrical wiring and devices must be done installed by author...

Страница 10: ...Boiler Installation Connection with a Thermoregulating Valve Boiler Installation Connection with a Heat Storage Tank...

Страница 11: ...he storage tank and the outdoor temperature Recommended heat storage unit sizes Boiler Type MA 15 MA 20 MA 25 MA 31 MA 40 MA 49 MA 80 Capacity kW 15 20 25 31 40 49 80 Volume l 1000 1000 1500 1500 2000...

Страница 12: ...WATTS STS 20 connected to water supply piping In the event you use your own well you can protect your boiler using a backup electric power source to sustain the operation of at least one pump Another...

Страница 13: ...before you fill up the boiler with heating water The Danfoss BVTS Honeywell TS 130 or the WATTS STS 20 valve the sensor of which is located in the lateral part of the boiler is intended to protect the...

Страница 14: ...18 CONTROL UNIT ERS AK 6000 AK 6000 Maga Wood Gasifying Boilers Control System User Manual...

Страница 15: ...outlet Do not operate the boiler unless all enclosure panels are properly in place In case of failure detection or damaging any part is important o do not touch any part of boiler o immediately discon...

Страница 16: ...l suply ending after fuel suply is passed by menu level or choice confirmation data storage o long 2 sec pressing entrance to user operation settings button decreasing adjusted value or switching depi...

Страница 17: ...peed in suction version or to 0 in blower version Combustion Continuous regulation of the fan keeps the boiler temperature on the acquired value Critical values of temperatures and thermostat automati...

Страница 18: ...r and make all required action Short press the ENTER boiler gets in original state again End of the combustion Combustion temperature decreases under the minimal value boiler is automatically turned O...

Страница 19: ...two seconds long Basic view goes to the frame 1 where we use short click on the ENTER and we are in the frame 1 1 Short click of the ENTER and we can set required temperature by buttons or in 70 85 C...

Страница 20: ...ut It keeps the embers waiting 50 130 C Main fan power change For example value 3 decreases fan speed in 30 3 2 2 3 Fan minimal speed This value is limit for speed decrease of the fan after reaching r...

Страница 21: ...ouble click of the ESC All the connected accsesories are monitored by system Common error status is displayed by red color of the LED More exactly is error message displayed on the LCD display in the...

Страница 22: ...t basic view we must hold the button ENTER two seconds long One click on the button will get us to the frame 6 By means of the ENTER button we can enter into the version display By means of the ENTER...

Страница 23: ......

Страница 24: ...n date Stamp and signature of the producer Date of sale Stamp and signature of the seller Date of putting into operation Stamp and signature Letter of guarantee is not valid unless properly filled in...

Страница 25: ...of product Guarantee does not include any materials that are subject to common wear and tear sealing and packing rope fire concrete block and filling and sibral filling Guarantee will not be granted...

Страница 26: ...Record of performed guarantee repairs Record of performed repairs within guarantee period and after Date of the record Performed activity Organization signature stamp Signature of the customer...

Страница 27: ...MA 15 MA 20 MA 25 MA 31 MA 40 MA 49 MA 80 Producer MAGA s r o S KOLL RA 86 EREN ANY 979 01 RIMAVSK SOBOTA SLOVAKIA Above mentioned products are compatible with the following standards EN 303 5 2001 S...

Отзывы: