background image

 

 

1.

 

Purpose of Use 

The MA hot-water boiler is intended for heating homes and other types of buildings. The boiler is designed exclusively to 

work on burning  wood.  Any  dry  wood such as chopped logs or  wood chips  with  maximum  length of 500  mm  (MA 15  – 350 
mm, MA 80 – 650 mm) can be used as fuel for this boiler. Recommended log diameter is 150 mm.  Logs with larger diameters 
can be used as well (max. 200 mm). If so done, the boiler’s rated output capacity will decrease and the period of burning will be 
extended Minimal diameter of wood chops is 60mm. In case these parameters are not met, extreme overheating of boiler may 
occur in the burn-out chamber  and ceramic parts will be damaged consequently due to enormous heat. 

  

 

A large wood storage bin will help replace and eliminate the most laborious operations associated with the preparation of 

wood  fuel  –  i.e.  the  sawing  and  cutting  of  logs  into  pieces  of  an  appropriate  size.  This  practice  will  save  not  only  physical 
exertion, but also time necessary for the work.            

2.

 

Technical Parameters 

Boiler Type  

 

 

 

 

 

MA 15   

MA 20   

MA 25

 

 
Output Capacity   

 

 

kW 

 

15 

 

20 

 

25 

Maximum Output Capacity 

 

kW 

 

18 

 

22 

 

27 

Heating Surface   

 

 

sq. m.   

1,45 

 

1,75 

 

1,95 

Fuel Bin Volume  

 

               cubic dm (dm

3

)  75 

 

110 

 

125 

Operating Draught  

 

 

Pa  

 

10-15 

 

10-15 

 

10-15 

Maximum Operating Water Gauge Pressure (MPa)   

0,25 

 

0,25  

 

0,25 

Boiler Weight    

 

 

kg 

 

310 

 

350  

 

380 

Exhaust Socket Diameter   

 

mm 

 

159 

 

159 

 

159 

Boiler Height 

 

 

 

mm 

 

1120 

 

1120 

 

1210 

Boiler Depth  

 

 

 

mm 

 

1000 

 

1140 

 

1140 

Boiler Width   

 

 

 

mm 

 

570 

 

570 

 

570 

Water capacity   

 

 

 

65 

 

70 

 

75 

Boiler Efficiency  

 

 

 

 

 

at  Rated Capacity 

 

 

 

85 

 

85 

 

85 

Prescribed Type of Fuel  

Dry wood calorific value of 15-17 MJ / kg 

 water content  

min. 12% - max. 20% diameter 90-150 mm 

Average Fuel Consumption 

 

kg . h

-1

   

4,2 

 

5,8 

 

6,2 

Maximum length of wood logs/chips  

 

 

 

 

 

ø 60 – 200 mm   

 

 

mm 

 

350 

 

500 

 

500 

Degree of coverage of the electric part  

IP 

 

20  

 

20 

 

20 

Voltage   

 

 

 

V / Hz   

230/50   

230/50   

230/50 

Fan power input   

 

 

 

77 

 

77 

 

77 

 

Boiler Type  

 

 

 

 

 

MA 31  MA 40   MA 49   

MA 80

 

 

 

 

 

 

 

 

 

   

 

 

Output Capacity   

 

 

kW 

 

31 

   40  

49 

 

75 

Maximum Output Capacity 

 

kW 

 

33 

   42 

52 

 

80 

Heating Surface   

 

 

sq. m.   

2,35 

   3,6 

4,1 

 

7,3 

Fuel Bin Volume  

 

 

cubic dm (dm

3

)  140 

  140 

190 

 

300 

Operating Draught  

 

 

Pa  

 

15-20 

  15-20  15-20 

 

20-25 

Maximum Operating Water Gauge Pressure (MPa)   

0,25 

   0,25  0,25  

 

0,25 

Boiler Weight    

 

 

kg 

 

430 

   510 

550  

 

810 

Exhaust Socket Diameter   

 

mm 

 

159 

   159 

159 

 

159 

Boiler Height 

 

 

 

mm 

 

1210 

   1290  1290 

 

1425 

Boiler Depth  

 

 

 

mm 

 

1140 

   1140  1165 

 

1380 

Boiler Width   

 

 

 

mm 

 

620 

   620 

730 

 

730 

Water capacity   

 

 

 

80 

 90 

110 

 

180 

Boiler Efficiency  

 

 

 

 

 

at  Rated Capacity 

 

 

 

85 

 85 

85 

 

85 

Prescribed Type of Fuel    

 

 

 

Dry wood calorific value of 15-17 MJ / kg  

water content  

min. 12% - max. 20% diameter 90-150 mm 

Average Fuel Consumption 

 

kg . h

-1

   

7,8 

  9,1 

9,8 

 

18,6 

Maximum length of wood logs/chips  

 

 

 

 

 

ø 60 – 200 mm   

 

 

mm 

 

500 

  500 

500 

 

650 

Degree of coverage of the electric part  

IP 

 

20  

   20 

20 

 

20 

Voltage   

 

 

 

V / Hz   

230/50   230/50  230/50   

230/50 

Fan power input   

 

 

 

77 

   77 

120 

 

120 

Содержание MA 15

Страница 1: ...MA 31 MA 40 MA 49 MA 80 With an exhaust fan and CONTROL UNIT ERS AK 6000 BOILER OPERATION AND MAINTENANCE MANUAL MAGA s r o S Koll ra 86 979 01 eren any Rimavsk Sobota Slovakia Tel fax 421 47 56 34 79...

Страница 2: ...and a minimum return water temperature of 60 C 140 F The pump must be connected to the thermo switch in such a way that it only operates when the required minimum temperature is reached 4 The boiler m...

Страница 3: ...25 0 25 Boiler Weight kg 310 350 380 Exhaust Socket Diameter mm 159 159 159 Boiler Height mm 1120 1120 1210 Boiler Depth mm 1000 1140 1140 Boiler Width mm 570 570 570 Water capacity l 65 70 75 Boiler...

Страница 4: ...red boiler must be operated in accordance with the instructions contained in this operating and maintenance manual The boiler must be operated by adults only CAUTION When you fire up a new boiler for...

Страница 5: ...y For the boilers MA approximate dimensions of the boiler s cross section are 20 x 20 cm Minimum height 7 m 20 cm Minimum height 8m Exact dimensions of a chimney for this purpose in Slovakia are gover...

Страница 6: ...al s such floor must be shielded with a thermally insulating fireproof board extending at least 300 mm beyond the ground plan on the firetending side and at least 100 mm beyond the ground plan on all...

Страница 7: ...nce to a boiler that is currently under operation When operating a solid fuel fired boiler no inflammable liquids are permitted to be used for firing up Increasing in any manner a boiler s output capa...

Страница 8: ...et 9 Primary air inlet 10 Ceramics nozzle 11 Firing flap valve 12 Primary air inlet duct 13 Clean out cover 14 Smoke flue outlet 15 Firing valve s draw rod 16 Fuse 17 Chimney sensor flue gas temperatu...

Страница 9: ...lly or through an electronic regulating device that will provide a more comfortable and more economic operation of the boiler Any related electrical wiring and devices must be done installed by author...

Страница 10: ...Boiler Installation Connection with a Thermoregulating Valve Boiler Installation Connection with a Heat Storage Tank...

Страница 11: ...he storage tank and the outdoor temperature Recommended heat storage unit sizes Boiler Type MA 15 MA 20 MA 25 MA 31 MA 40 MA 49 MA 80 Capacity kW 15 20 25 31 40 49 80 Volume l 1000 1000 1500 1500 2000...

Страница 12: ...WATTS STS 20 connected to water supply piping In the event you use your own well you can protect your boiler using a backup electric power source to sustain the operation of at least one pump Another...

Страница 13: ...before you fill up the boiler with heating water The Danfoss BVTS Honeywell TS 130 or the WATTS STS 20 valve the sensor of which is located in the lateral part of the boiler is intended to protect the...

Страница 14: ...18 CONTROL UNIT ERS AK 6000 AK 6000 Maga Wood Gasifying Boilers Control System User Manual...

Страница 15: ...outlet Do not operate the boiler unless all enclosure panels are properly in place In case of failure detection or damaging any part is important o do not touch any part of boiler o immediately discon...

Страница 16: ...l suply ending after fuel suply is passed by menu level or choice confirmation data storage o long 2 sec pressing entrance to user operation settings button decreasing adjusted value or switching depi...

Страница 17: ...peed in suction version or to 0 in blower version Combustion Continuous regulation of the fan keeps the boiler temperature on the acquired value Critical values of temperatures and thermostat automati...

Страница 18: ...r and make all required action Short press the ENTER boiler gets in original state again End of the combustion Combustion temperature decreases under the minimal value boiler is automatically turned O...

Страница 19: ...two seconds long Basic view goes to the frame 1 where we use short click on the ENTER and we are in the frame 1 1 Short click of the ENTER and we can set required temperature by buttons or in 70 85 C...

Страница 20: ...ut It keeps the embers waiting 50 130 C Main fan power change For example value 3 decreases fan speed in 30 3 2 2 3 Fan minimal speed This value is limit for speed decrease of the fan after reaching r...

Страница 21: ...ouble click of the ESC All the connected accsesories are monitored by system Common error status is displayed by red color of the LED More exactly is error message displayed on the LCD display in the...

Страница 22: ...t basic view we must hold the button ENTER two seconds long One click on the button will get us to the frame 6 By means of the ENTER button we can enter into the version display By means of the ENTER...

Страница 23: ......

Страница 24: ...n date Stamp and signature of the producer Date of sale Stamp and signature of the seller Date of putting into operation Stamp and signature Letter of guarantee is not valid unless properly filled in...

Страница 25: ...of product Guarantee does not include any materials that are subject to common wear and tear sealing and packing rope fire concrete block and filling and sibral filling Guarantee will not be granted...

Страница 26: ...Record of performed guarantee repairs Record of performed repairs within guarantee period and after Date of the record Performed activity Organization signature stamp Signature of the customer...

Страница 27: ...MA 15 MA 20 MA 25 MA 31 MA 40 MA 49 MA 80 Producer MAGA s r o S KOLL RA 86 EREN ANY 979 01 RIMAVSK SOBOTA SLOVAKIA Above mentioned products are compatible with the following standards EN 303 5 2001 S...