DECLARATION OF PERFORMANCES
2
02/18
V10/18
Fire damper
“FOK-EIS-120”
Madel Air Technical Diffusion S.A,
C/ Pont de les Bruixes P-5, P.I. La Gavarra, 08540 CENTELLES
(Barcelona)
To prevent fire and reduce smoke spreading from one fire
compartment to
another through the air ductwork system which may penetrate fire
separating
vertical compartments, according to Standard EN 15650:2010
(annex ZA.1).
System 1, according to Construction Products Regulation nº
305/2011
APPLUS - 0370
Performed tasks:
- Determination of the product type on the basis of type testing
(including
sampling), type calculation, tabulated values or descriptive
documentation of the
product;
- Initial inspection of the manufacturing plant and of factory
production control;
- Continuous surveillance, assessment and evaluation of factory
production control.
System 1
Certification number: 0370
– CPR – 1380
Test report:
11/3034-2632, 12/5477-1359, 14/8629-797, 17/12815-16,
18/12815-1800, 14/8629-947, 18/12815-700, 18/12815-701,
18/12815-703, 18-17552-1206
6. Performances (EN 15650 :2010):
Performances
Dimensions
Type
Wall
Type of
installation
Mechanism
orientation
Class
Rigid wall
Brick wall/ reinforced concrete wall
≥ 150 mm
Built-in
0-180º
EI 120 (v
e
i
↔o) S (500Pa)
Rigid wall
Plasterboard type F (s/ EN 520)
108 (15x2 + 48 (LM 50Kg/m
3
) + 15x2)
Built-in
0-180º
EI 120 (v
e
i
↔o) S (500Pa)
Rigid floor
Reinforced concrete floor
≥ 150 mm
Built-in
0-360º
EI 120 (v
e
i
↔o) S (500Pa)
Rigid wall
Muro de obra/ Hormigón armado
≥ 150 mm
Built-in
0-180º
EI 120 (v
e
i
↔o) S (500Pa)
Rigid floor
Reinforced concrete floor
≥ 200 mm
Built-in
0-360º
EI 120 (h
o
i
↔o) S (300Pa)
Sensing element load bearing capacity
Sensing element response temperature
Closure time
50 cycles
…- /MA/ - 300 cycles, …-/MAF/ - 300 cycles,
…- /MFS…V/ - 10.200 cycles, …- /MFB…V/ - 10.200 cycles
Sensing element response temperature and load bearing capacity
Opening and Closing cycle
DECLARATION OF PERFORMANCE (Nº 0370-CPR-1380)
Approved
Approved
Approved
Joan Arcarons Alibés
(Technical Director)
Durability of operational reliability according to 15650:
7. The performances of the product identified in point 1, are in line with the declared performance in point 6.
This declaration of performance is issued under the responsibility of the
manufacturer listed in point 2.
Signed for and on behalf of the manufacturer:
Centelles, 22/10/18
Nominal activation conditions/ sensitivity:
Response delay according to EN 1366-2:
Approved
Durability of response delay according to EN1366-2:
4. Assessment of conformity system:
Operational reliability according to EN 1366-2
3. Uses to:
2. Name and address of manufacturer:
1. Product and identification name:
Essential characteristics
Cycling (opening and closing) on fire test.
Cycling (opening and closing) according to Standard for CE Marking
5. Certification body:
200 x 200
a
1000 x 600
200 x 200
a
1500 x 800