Macurco DVP-120C Manual
REV – 1.0
[34-8708-4770-8 ]
9
|
P a g e
2.4
Features
•
LCD display showing the status of each transducer and relay
•
External keypad for user selection of the transducer/alarm display and setting the configuration (password
protected)
•
Up to three ventilation control zones can be defined
•
Each zone can be controlled based on transducer signals and/or time of day
•
Each relay is configurable with a delay before activation and minimum on time
•
Fail-safe operation can be implemented
•
Lockable NEMA 1 type enclosure
•
Modular input and output connectors
•
One RS-485 digital input channels - 99 addressable sensors
•
RS-485 digital output channel for BACnet
•
Compatible with Macurco CM-6, TX-6-ND, and MRS-485 adapter, Horn & Strobe Combo
•
Three 10A, 240 VAC SPDT Dry Contact relays
•
24VDC Drivers for external Horn and Strobe
•
BTL Listed
•
ETL Listed to UL 2017
1
(Type SM)
1
Where required by federal, state, local regulations or the Authority Having Jurisdiction, DVP-120C is required to be used with Listed
Horn/Strobe model 78-2900-0211-X* to meet the 85dB(A) Audibility requirements of Standards UL 2017.
*
Where “X” represents lens cover color, R for red lens cover, G for green lens cover, B for blue lens cover, O for amber lens cover, C for
clear lens cover.
2.5
Specifications
•
Size: 10.5” x 12.5” x 2.” (267 mm x 318 mm x 51 mm)
•
Weight:
6 ½ lb (2.9 kg)
•
Enclosure:
NEMA 1 Type
•
Operating Temperature:
32° to 120°F (0° to 49°C)
•
Operating Humidity:
0% to 90% RH non-condensing
•
Power Input: 90 – 250 VAC, 1 Amp, 47 – 63 Hz, single phase
•
Relay Rating (3):
SPDT, 120/240 VAC, 10 A resistive
•
LCD Display: 2 rows of 16 characters with backlight
•
Status Indicators (LED): Power/Trouble, ALARM/warning, Hush, Relay 1, Relay 2 & Relay 3
•
Audible indicator:
Internal buzzer, 90 dBA at 1ft
•
External Drivers (2):
24VDC, maximum 250 mA
•
Carbon Monoxide (CO) Range: 0 – 200ppm
•
Nitrogen Dioxide (NO2) Range: 0 – 20ppm
•
Relay on Delay: 0 – 15 minutes in 1 second increments
•
Relay Minimum Run Time:
0 – 15 minutes in 1 second increments
Содержание MRS-485
Страница 2: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 2 P a g e ...
Страница 77: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 77 P a g e 11 Appendix D DVP 120 Quick Start Guide ...
Страница 78: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 78 P a g e ...
Страница 79: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 79 P a g e ...