Figure 4-54 Sensor Summary
This display example shows that the sensor on channel 01 has been configured as a Carbon Monoxide Sensor. The
valid entries for Macurco type sensors are Carbon Monoxide (CO), and Nitrogen Dioxide (NO
2
).
Setting the sensor type to 0 (zero) will cause the display to ask if the user wants to DELETE the sensor. If the answer
is yes, the configuration record for this sensor channel will be deleted and the channel will no longer be used to
control the ventilation system. When a sensor’s type is changed, the alarm level, warning level, and range will be set
to the default for the sensor type.
The following three parameters are not accessible until a sensor type of 1, or 2 is selected.
4.13.3.3
Alarm Set Point
S e n s o r 0 1 C O
A l a r m : 2 0 0 p p m
Figure 4-55 Sensor Alarm Level
The default alarm levels for the sensors are:
Description
Carbon
Monoxide
Nitrogen
Dioxide
Alarm
Level
200ppm
5ppm
Table 4-5 Default Alarm levels
Setting an alarm level of 0 (zero) will disable alarm detection for this sensor.
4.13.3.4
Warning Set Point
S e n s o r 0 1 C O
W a r n i n g : _ 5 0 p p m
Figure 4-56 Sensor Warning Level
The default warning levels for the sensors are:
Description Carbon
Monoxide
Nitrogen
Dioxide
Warning
Level
100 ppm
3 ppm
Table 4-6 Default warning levels
Setting a warning level of 0 (zero) will disable warning detection for this particular sensor.
4.13.3.5
Range
S e n s o r 0 1 C O
R a n g e : 2 0 0 p p m
Figure 4-57 Sensor Range
The range for each sensor is the gas concentration that corresponds to the 20-mA signal level.
Содержание DVP-120C
Страница 2: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 2 P a g e ...
Страница 77: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 77 P a g e 11 Appendix D DVP 120 Quick Start Guide ...
Страница 78: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 78 P a g e ...
Страница 79: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 79 P a g e ...