Macurco DVP-120C Manual
REV – 1.0
[34-8708-4770-8 ]
68
|
P a g e
•
Relay 3
Normally off, 1-minute turn on delay, 1 minute minimum on time
•
Horn
Normally off, 1-minute turn on delay, 0 (zero) minimum on time
•
Strobe
Normally off, 1-minute turn on delay, 0 (zero) minimum on time
•
Zone1
Controls R1
•
Zone2
Controls R2
•
Zone3
Controls R3
•
Group 1 in each zone
Type 1 CO, Voting mode, Quorum = 1
•
Group 2 in each zone
Type 2 NO
2
, Voting mode, Quorum = 1
Description
Carbon
Monoxide
Nitrogen
Dioxide
Type
CO
NO
2
Range
200 ppm
20 ppm
Alarm
Level
200 ppm
5 ppm
Warning
Level
100 ppm
3 ppm
Rising
Level
35 ppm
2.5 ppm
Falling
Level
15 ppm
1.2 ppm
Table B-1 Default settings
Typical coverage for CO, and NO
2
sensors is 5,000 sq. ft. (464.5 sq. m) (see the User Instructions for each sensor type
for location and coverage details). Extra sensors may be needed near areas where people work, such as toll booths.
Macurco provides only the control panels and sensors. Fans, relays, and other devices are provided by the
contractor. See the appropriate building code for the size of fans and air changes per unit of time.