REV – 1.0
[34-8708-4770-8 ]
34
|
P a g e
2
Sensors
Undefined
3
Alarm signals
Buzzer = Intermittent, Horn = Intermittent, Strobe = Continuous
4
Warning signals
Buzzer = Off, Horn = Off, Strobe = Off
5
Trouble signals
Buzzer = Triple Tap, Horn = Off, Strobe = Off
6
Relay 1
Normally off, 1-minute turn on delay, 1 minute minimum on time
7
Relay 2
Normally off, 1-minute turn on delay, 1 minute minimum on time
8
Relay 3
Normally off, 1-minute turn on delay, 1 minute minimum on time
9
Horn
Normally off, 1-minute turn on delay, 0 (zero) minimum on time
10
Strobe
Normally off, 1-minute turn on delay, 0 (zero) minimum on time
11
Zone 1
Controls R1
12
Zone 2
Controls R2
13
Zone 3
Controls R3
14
Group 1 in each zone Type 1 CO, Voting mode, Quorum = 1
15
Group 2 in each zone Type 2 NO2, Voting mode, Quorum = 1
Description
Carbon
Monoxide
Nitrogen
Dioxide
Type
CO
NO
2
Range
200ppm
20ppm
Alarm Level
200ppm
5ppm
Warning
Level
100ppm
3ppm
Rising Level
35ppm
2.5ppm
Falling Level
15ppm
1.2ppm
Table 4-3 Default Configuration Settings
4.13.2.4
Change Password
C h a n g e P a s s w o r d
* * * *
Figure 4-29 Change Password
When the first digit is entered to change the password, the panel will prompt for the existing password to be
entered (if it hasn’t already been entered), see section
for more detail. Once the current
password has been entered, the panel will prompt for the new password.
4.13.2.5
Configure Modbus
B a u d R a t e:
0 - 1 9 2 0 0 B d
Содержание DVP-120C
Страница 2: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 2 P a g e ...
Страница 77: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 77 P a g e 11 Appendix D DVP 120 Quick Start Guide ...
Страница 78: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 78 P a g e ...
Страница 79: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 79 P a g e ...