Figure 4-44 Resolution
“Res.” Defines the resolution used to display the reading, alarm, warning, range, falling level and rising level. It can
have values between 1 and 500 when “Dec.” is 0, 50.0 when “Dec.” is 1 and 5.00 when “Dec.” is 2.
Type: 01 CO
Range:
200 ppm
Figure 4-45 Sensor Range
“Range” is the value displayed when current measured is 20mA.
Type: 01 CO
Alarm:
200 ppm
Figure 4-46 Alarm Level
“Alarm” is the default alarm range.
Type: 01 CO
Warn:
100 ppm
Figure 4-47 Warning Level
“Warn” is the default warning range.
Type: 01 CO
Rise:
35 ppm
Figure 4-48 Rising Trip Point
“Rise” is the default rising level used in Zone configuration.
Type: 01 CO
Fall:
15 ppm
Figure 4-49 Falling Trip Point
“Fall” is the default falling level used in Zone configuration.
4.13.2.8
Enter Password
If the password has not yet been entered, when the first digit of any parameter is entered, the panel will prompt for
the current password. Note that the first digit entered is discarded; it does not count toward the password or
toward the parameter entry.
E n t e r P a s s w o r d
_ _ _ _
Figure 4-50 Enter Password
When the first digit is entered, the panel will show
E n t e r P a s s w o r d
_ _ _ *
Содержание DVP-120C
Страница 2: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 2 P a g e ...
Страница 77: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 77 P a g e 11 Appendix D DVP 120 Quick Start Guide ...
Страница 78: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 78 P a g e ...
Страница 79: ...Macurco DVP 120C Manual REV 1 0 34 8708 4770 8 79 P a g e ...