56
Default - Minimum Runtime - 1 Minute
R e l a y 1 M i n . O n
( m m : s s ) 0 1 : 0 0
Figure A-20 Minimum on Time
→
Relay 2 - repeat for all relays, horn, and strobe
8.4
Configure Zones Submenu
8.4.1
Definitions:
Zone – Defines Sensor Input & Relay / Alarm Output
Group – Set of Sensors of the same type and output within the same zone
Average – Activation based upon an average of sensors in a group
Voting – Number of sensors needed to be above trip point to activate the output
Quorum – Number of sensors need to vote, 1 = any sensor
Press Menu to display Hardware Summary
↑
x 4 Configure Zones
→
Zone 1 Controls
R_ R_ R_ H_ S_
Enter (underlined) number of output for zone
R = Relay (1, 2 and 3), H = Horn (4), S = Strobe (5)
Z o n e 1 C o n t r o l s
R 1 R 2 R 3 H 4 S 5
Figure A-21 Zone Controls
↑
Configure Group 1
Sensor type - enter #
1=CO, 2=NO2, 3=Combustible, 0=None
Z 1 G r o u p 1 N O 2
S e n s o r T y p e : 2
Figure A-22 Zone Controls
↑
Sensor Number - enter a two-digit number for each sensor to be included in the group (e.g., 01, 02, 03…12.) from 01 through 12.
Z 1 G r o u p 1 N O 2
S e n s o r s : 0 2 , 0 4 , 1 1
Figure A-23 Sensor Selection