Revision 0.07 

1.4  Specifications

1

 

 

Size: 

10” x 12” x 2” (254 mm x 305 mm x 51 mm) 

 

Weight: 

TBD 

 

Enclosure: 

Nema 1 equivalent steel 

 

Operating Temperature: 

0° to 50 °C (-32  to 122 °F) 

 

Operating Humidity: 

0% to 95% RH non-condensing 

 

Power Input: 

100 – 240 VAC, 1 Amp, 47 – 63 Hz, single phase 

 

Relay Rating (3): 

SPDT, 120/240 VAC, 16 A resistive 

 

LCD Display:  

2 rows of 16 characters with backlight  

 

Status Indicators (LED): 

Power, ALARM/warning, Silenced, Relay 1, Relay 2 & Relay 3  

 

Audible indicator: 

Internal buzzer, 90 dbA at 1ft 

 

External Drivers (2): 

24VDC, maximum 250 mA 

 

CO Transducer Range: 

0 – 250PPM 

 

NO Transducer Range: 

0 – 9.0 PPM 

 

EX Transducer Range: 

0 – 10,000 PPM 

 

Relay On Delay: 

0 – 15 minutes in 1 second increments 

 

Relay Off Delay: 

0 – 15 minutes in 1 second increments 

1.5  Warranty 

The DVP-120 Gas Detection and Ventilation Control Panel is warranted to be free from defective material and 
workmanship for a period of two (2) years  from  the date of manufacture (stamped on the unit). If any 
component becomes defective during the warranty period, it will be replaced or repaired free of charge, if the 
unit is returned in accordance with the instructions below. This warranty does not apply to units that have been 
altered or had repair attempted, or that have been subjected to abuse, accidental or otherwise. The above 
warranty is in lieu of all other express warranties, obligations, or liabilities.  

THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE 
ARE LIMITED TO A PERIOD OF TWO (2) YEARS FROM THE PURCHASE DATE.  

Macurco shall not be liable for any incidental or consequential damages for breach of this or any other warranty 
express or implied, arising out of or related to the use of the control panel. Manufacturer or its agent’s liability 
shall be limited to replacement or repair as set forth above. Buyer’s sole and exclusive remedies are return of 
the goods and repayment of the price, or repair and replacement of non-conforming goods or parts. (The 
Uniform Commercial Code applicable in the State of Colorado shall govern) 

1.6  Return Instructions 

Call (303) 781-4062 for a Return Authorization form. Then carefully pack the control panel with a written 
description of the nature of the return. Send the unit to the following address: 

Aerion Technologies Inc. 

6555 S. Kenton St., Ste 304 

Centennial, CO 

USA 80111 

                                                           

1

 Macurco reserves the right to modify or change the specifications of all products without prior 

notification to the user. 

Содержание DVP-120

Страница 1: ...DVP 120 Installation Operating Instructions...

Страница 2: ...ystem Submenu 21 3 3 3 Configure Sensors Submenu 24 3 3 4 Configure Relays Horn Strobe Submenu 26 3 3 5 Configure Horn Submenu 27 3 3 6 Configure Strobe Submenu 28 3 3 7 Configure Zones Submenu 29 3 3...

Страница 3: ...26 Figure 3 31 Turn On Delay 26 Figure 3 32 Minimum on time 26 Figure 3 33 Horn Summary 27 Figure 3 34 Horn Mode 27 Figure 3 35 Horn Turn On Delay 27 Figure 3 36 Horn Minimum on time 27 Figure 3 37 St...

Страница 4: ...2 3 Connector to Sensor Channel Mapping 11 Table 2 4 Sensor Connectors Channel and Pin Assignments 11 Table 2 5 Relay Interface Signals and Connector Assignments 12 Table 2 6 Horn Strobe signals and...

Страница 5: ...configured sensor In addition all control functions of the DVP 120 may be accessed through the system display and keypad 1 2 Features Twelve analog current loop input channels Three 16A 240 VAC SPDT...

Страница 6: ...T SPECIFICATIONS Gas detection and exhaust fan control is provided by a Macurco DVP 120 system This System will use CM 2B or CM 3 Carbon Monoxide CO to current transducers ND 2 Nitrogen Dioxide to cur...

Страница 7: ...Revision 0 07 7 Figure 1 2 DVP 120 Internal View...

Страница 8: ...s below This warranty does not apply to units that have been altered or had repair attempted or that have been subjected to abuse accidental or otherwise The above warranty is in lieu of all other exp...

Страница 9: ...ualified technicians should open the DVP 120 case and service the internal circuits Ensure power is removed from the DVP 120 prior to servicing the unit With the exception of the safety ground all fie...

Страница 10: ...ctor into J4 on the PCB and ensure that it latches into the header properly Signal Terminal Connection Line 120 220 240 250 VAC J4 3 Neutral J4 1 Ground Ground Stud Table 2 1 Main Power Connections 2...

Страница 11: ...r Pin Number CH 1 24 Vdc J7 5 CH 5 24 Vdc J13 5 CH 9 24 Vdc J11 5 CH 1 I loop J7 6 CH 5 I loop J13 6 CH 9 I loop J11 6 CH 1 I loop J7 7 CH 5 I loop J13 7 CH 9 I loop J11 7 CH 1 24Vdc Ret J7 8 CH 5 24V...

Страница 12: ...the insulation of each wire back approximately 1 4 in 6 5 mm insert the bare wire into the terminal and tighten the screw clamp Ensure that the wire cannot easily be pulled from the connector Note tha...

Страница 13: ...are wire into the terminal and tighten the screw clamp Ensure that the wire cannot easily be pulled from the connector When all wires are connected seat the modular connector into the PCB header ensur...

Страница 14: ...e since a bridge rectifier is connected to the power input terminals All sensors used with the DVP 120 panel employ screw clamp terminal blocks for power and signal connections Polarity of the current...

Страница 15: ...During the warm up period the keypad will be locked When the warm up period ends the LCD will start showing the normal display Figure 3 4 3 1 1 Status Light Display The POWER ALARM WARNING SILENCE REL...

Страница 16: ...or down key is again used the display will switch back to the digit keys jumping to a particular sensor The MENU key has three functions First when the system is presenting the normal display pressing...

Страница 17: ...her than prompting to show the relay If the sensor is indicating a gas level that is greater than the alarm or warning levels the gas reading will alternate with the words ALARM or WARNING as appropri...

Страница 18: ...ble delay for the horn or strobe will sound see sections 3 3 5 3 and 3 3 6 3 When the HUSH key is pressed the internal buzzer will be silenced for fifteen 15 minutes If the horn or strobe turn on dela...

Страница 19: ...ays and the external horn and strobe if desired When more than one zone is controlling a relay it only takes one zone to activate the relay but all controlling zones must release the relay before it w...

Страница 20: ...ckground with the previously set configuration values In particular if an alarm condition is detected the alarm lamp the buzzer the horn and the strobe will operate as configured but the LCD will not...

Страница 21: ...ample shows that the time is 22 55 10 55 PM The underlined characters indicate that the numeric keys can be used to set the current time of day When the first digit is entered and after the password i...

Страница 22: ...in another The default configuration is Password 1234 Sensors Undefined Alarm levels CO 200 ppm HS 5 0ppm EX 4 000 ppm Alarm signals Buzzer Intermittent Horn Intermittent Strobe Continuous Warning si...

Страница 23: ...hen the first digit is entered the panel will show P a s s w o r d _ _ _ 1 Figure 3 22 Password Prompt If the password is not entered correctly the panel will display W r o n g P a s s w o r d Figure...

Страница 24: ...25 Sensor Type This display example shows that the sensor on channel 01 has been configured as a Carbon Monoxide sensor The valid entries for the sensor type are 1 Carbon Monoxide CO 2 Nitrogen Dioxi...

Страница 25: ...000 ppm 5 LEL for methane Setting a warning level of 0 zero will disable warning detection for this particular sensor 3 3 3 5 Range S e n s o r 0 1 C O R a n g e _ 2 0 0 p p m Figure 3 28 Sensor s Ra...

Страница 26: ...Off mode The relay modes are 1 ALARM 2 Normally Off default 3 Normally On Relay mode 1 is a special case This mode is only available on relay 1 and dedicates the relay to function as an alarm signal t...

Страница 27: ...eys can be used to jump to a particular relay horn or strobe The relays are numbers 1 2 and 3 the horn is number 4 and the strobe is 5 3 3 5 2 Horn Mode H o r n N o r m O f f M o d e 2 Figure 3 34 Hor...

Страница 28: ...can be used to jump to a particular relay horn or strobe The relays are numbers 1 2 and 3 the horn is number 4 and the strobe is 5 3 3 6 2 Strobe Mode S t r o b e N o r m O f f M o d e 2 Figure 3 38 S...

Страница 29: ...by pressing the indicated digit key By default all three zones are configured not to control any devices When a new panel is first powered up this display will not show the digits only the underlined...

Страница 30: ...2 0 4 1 1 Figure 3 46 Sensor Selection Sensors are included or removed from the group by entering the two digit channel number After a sensor is added or removed the list will be re sorted so it does...

Страница 31: ...one outputs s are activated When the average is less than or equal to the falling trip point the zone output s are de activated If the average is between the two trip points the outputs remain in ther...

Страница 32: ...ternal horn and the strobe 3 3 8 2 Alarm Buzzer Signal A l a r m S i g n a l s B u z z 2 I n t e r m i t Figure 3 53 Buzzer Alarm Signal This display example shows that the buzzer will signal an alarm...

Страница 33: ...are signaled by the internal Buzzer only 3 3 8 6 Warning Buzzer Signal W a r n i n g S i g n a l s B u z z 5 O F F Figure 3 57 Buzzer Warning Signal This display example shows that the buzzer will not...

Страница 34: ...rnal Buzzer only 3 3 8 10 Trouble Buzzer Signal T r o u b l e S i g n a l s B u z z 4 T r i p l e Figure 3 61 Buzzer Trouble Signal This display example shows that the buzzer will signal a trouble con...

Страница 35: ...uble Signal This display example shows that the strobe will not signal a trouble condition The signal definitions are 1 Continuous 2 Intermittent one second on at two second intervals 3 Double Tap two...

Страница 36: ...a trouble message on the digital display Macurco sensors may be tested by depressing the TEST button on the sensor printed circuit board or depending on the type of sensor the button on the interior...

Страница 37: ...REPLACE THE SAFETY COVER on F3 before re applying power to the DVP 120 4 4 LCD Display unreadable It is possible that the LCD is unreadable due to temperature or aging of the control panel If this is...