Revision 0.07
22
3.3.2.2
Set Day of Week
T i m e : 2 2 : 5 5
D a y : 2 T u e s d a y
Figure 3-19 Set Day of the week
This display example shows that Tuesday is the current day of the week. The underline character indicates that
the day can be changed by entering the corresponding digit:
–
1
Monday
–
2
Tuesday
–
3
Wednesday
–
4
Thursday
–
5
Friday
–
6
Saturday
–
7
Sunday
3.3.2.3
Load Default Configuration
1 L o a d D e f a u l t
C o n f i g u r a t i o n
Figure 3-20 Load Default Configuration
When the one (1) digit is pressed, the panel will prompt for the password, even if it has been entered previously.
If the password is entered correctly, the panel will overwrite the existing configuration with the default
configuration. This operation is intended to restore the panel to a known basic condition if it is removed from
one installation and installed in another.
The default configuration is:
?
Password
1234
?
Sensors
Undefined
?
Alarm levels
CO = 200 ppm, HS = 5.0ppm, EX = 4,000 ppm
?
Alarm signals
Buzzer = Intermittent, Horn = Intermittent, Strobe = Continuous
?
Warning signals
Buzzer = Double Tap, Horn = Off, Strobe = Off
?
Trouble signals
Buzzer = Triple Tap, Horn = Off, Strobe = Off
?
Warning Levels
CO = 200 ppm, HS = 5.0 ppm, EX = 4,000 ppm
?
Sensor Range
CO = 200ppm, HS = 6.0 ppm, EX = 10,000 ppm
?
Relay 1
Normally off, 1 minute turn on delay, 1 minute minimum on time
?
Relay 2
Normally off, 1 minute turn on delay, 1 minute minimum on time
?
Relay 3
Normally off, 1 minute turn on delay, 1 minute minimum on time
?
Horn
Normally off, 1 minute turn on delay, 0 (zero) minimum on time
?
Strobe
Normally off, 1 minute turn on delay, 0 (zero) minimum on time
?
Zone1
Controls nothing, no sensors assigned, Voting mode, Quorum = 1
?
Zone2
Controls nothing, no sensors assigned, Voting mode, Quorum = 1
?
Zone3
Controls nothing, no sensors assigned, Voting mode, Quorum = 1
?
Rising Trip Levels CO = 100 ppm, HS = 2.5ppm, EX = 2,000 ppm
?
Falling Trip Levels CO = 50 ppm, HS = 1.2 ppm, EX = 1,000 ppm