6
Owner’s Manual
E
nglish
TO AVOID RISK OF ELECTRICAL SHOCK:
1. A green colored terminal or a terminal
marked G, GR, Ground, Grounding, or the
international symbol is located on
the side of the supply terminal box or
compartment. This terminal must be
connected to the grounding means
provided in the electric supply service
panel, using a continuous copper wire
equivalent in size to the circuit conductors
supplying this equipment.
*IEC Publication 417, Symbol 5019.
2. At least two lugs marked “BONDING
LUGS” are provided on the external sur-
face or on the inside of the supply termi-
nal box or compartment. Connect the
local common bonding grid (house-hold
ground) in the area of the hot tub or spa
to these terminals, using an insulated or
bare copper conductor not smaller than
No. 6 AWG.
3. All field-installed metal components such
as rails, ladders, drains or similar hard
ware located within 5 ft. of the spa or
hot tub shall be bonded to the equip-
ment grounding bus with copper con-
ductors not smaller than No. 6 AWG.
4.
Never
connect unit to a power supply
with a load controller.
5. Install to provide drainage of compart-
ment for electrical components.
6. The electrical supply for this product
must include a suitably rated switch
or circuit breaker to open all ungrounded
supply conductors. This disconnecting
means must be readily accessible for
operation but installed at least 1.5m
from the spa. All electrical connections
should comply with local regulations.
Caution: Risk of electrical shock. Read and follow all instructions.
SAVE ALL INSTRUCTIONS
NOTE: Check with your state/local code enforcement officer to determine electrical code
requirements and compliance. Use a qualified licensed electrician to complete all final spa
electrical connections.