7.3 Power, Ground, and Communication Cable Specification
Power Cable
0.75~1.5mm
2
(18~16AWG)
Ground Cable
1.5mm
2
(16AWG) or more
Conductor Type
Simple or Standard Wire
Bolt tightening force
≥
0.4N.m
Conductor Length
Temperature rating of the field installed
conductors
65℃ or under
- Power and ground terminal specifications are as follows. When installing the power and grounding terminals,
use the pin terminals to improve electrical transmission and to prevent the power line wearing.
B
L
F
E
D
d
1.8~2.0
22~18
12~14
5
3.3~3.8
2~2.5
- Attach the power cord to the power terminal of the body as follows.
7.4 Cradle Ground Wiring
(1) Although the instrument has sufficient noise countermeasures, in order to ensure the safety of the
instrument and the safety in use, the user must connect the ground of the instrument.
(2) Grounding should be done with a dedicated ground. It is recommended that the ground is a 3-class ground.
(Ground resistance is 100Ω or less)