background image

R7M-TS4

P. 3 / 7

EM-7803-B Rev.8

CONNECTION DIAGRAM

Connect the unit as in the diagram below.

4

7

6

3

2

5

1

0V

24VDC

FG

SLD

DG

DB

DA

10

+IN0

11

–IN0

1

+CJ0

2

–CJ0

+IN1

–IN1

+CJ1

–CJ1

+IN2

–IN2

+CJ2

–CJ2

+IN3

–IN3

+CJ3

–CJ3

INPUT 0

12

13

3

4

INPUT 1

15

16

6

7

INPUT 2

17

18

8

9

INPUT 3

■ 

Input Connection Example

+INn

–INn

+CJn

–CJn

T/C

+

CJC

SENSOR

+INn

–INn

Short

CJC

SENSOR

+CJn

–CJn

• 

Unused Input Channels

  Close across the unused input terminals as shown below.
   (Choose K (CA) thermocouple for unused channels.)

EXTENSION CONNECTOR

In order to improve EMC performance, bond the FG
terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.

WIRING INSTRUCTIONS

 

SCREW TERMINAL  

Torque

: 0.5 N·m

 

SOLDERLESS TERMINAL  mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminal:
Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd, Nichifu Co., Ltd

6 (.24) max

3.3 (.13) max

mm (inch)

MASTER CONNECTION

 MASTER CONNECTION

Tx+/Rx+
Tx–/Rx–

SG

Rx+
Rx–

Host PC

DA
DB

DG

SLD

FG

Remote Unit

DA
DB

DG

SLD

FG

Remote Unit

TERMINATOR

TERMINATOR

Be sure to connect the terminating resistor included in the product package to the unit at both ends of transmission line.
The terminator must be connected across DA and DB.
The Host PC can be located other than at the extreme ends of transmission line.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7M-TS4-R

Страница 1: ...nted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices and connected wires may affect the protection level of this u...

Страница 2: ...0 bps 3 4800 bps EXTENSION MODULE Combinations with all extension modules are selectable OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Discrete i...

Страница 3: ...WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL mm inch Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less ter...

Страница 4: ...ate both made of metal when installing the R7M Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielde...

Страница 5: ...d the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Страница 6: ...ons are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to th...

Страница 7: ...us Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To conn...

Отзывы: