background image

R7M-TS4

P. 2 / 7

EM-7803-B Rev.8

COMPONENT IDENTIFICATION

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

NODE ADD.

B.RATE

CNFG.

1

2

3

4

5

6

7

8

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

(A)  Status Indicator LED
(B)  Node Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  Modbus, Power Supply Terminals
(G)  Input Terminals

(A)

(F)

(G)

(B)

(C)

(D)

(E)

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

PWR

Red

Turns on when the internal 5V is supplied 
normally.

RUN

Red

Turns on when the data is received nor-
mally.

ERR

Red

Turns on when the received data is abnor-
mal. Blinks when setting is abnormal.

SD

Red

Turns on when the module is transmitting.

RD

Red

Turns on when the module is receiving.

 

NODE ADDRESS

Node Address is selected between 1 and 99 in decimal.  The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Factory setting : 00

Node Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0 : 38.4 kbps (factory setting)
1 : 19.2 kbps
2 : 9600 bps
3 : 4800 bps

 

EXTENSION MODULE

Combinations with all extension modules are selectable.

 

OPERATING MODE

(*) Factory setting

•  

Extension (SW1-1, 1-2)

SW1-1

SW1-2 EXTENSION

OFF

OFF

No extension (*)

ON

OFF

Discrete input, 8 or 16 points

OFF

ON

Discrete output, 8 or 16 points

• 

Conversion Rate (SW1-3)   • Burnout (SW1-4)

SW1-3 CONVERSION RATE

SW1-4 BURNOUT

OFF

250 msec. (*)

OFF

Upscale (*)

ON

500 msec.

ON

Downscale

• 

Thermocouple Type (SW1-5, 1-6, 1-7, 1-8)

SW1-5

SW1-6

SW1-7

SW1-8 THERMOCOUPLE TYPE

OFF

OFF

OFF

OFF

K (CA) (*)

ON

OFF

OFF

OFF

E (CRC)

OFF

ON

OFF

OFF

J (IC)

ON

ON

OFF

OFF

T (CC)

OFF

OFF

ON

OFF

B (RH)

ON

OFF

ON

OFF

R

OFF

ON

ON

OFF

S

ON

ON

ON

OFF

C (WRe 5-26)

OFF

OFF

OFF

ON

N

ON

OFF

OFF

ON

U

OFF

ON

OFF

ON

L

ON

ON

OFF

ON

P (Platinel II)

OFF

OFF

ON

ON

(PR)

ON

ON

ON

ON

PC Configurator setting

 

POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT

4

DA

5

DG

6

+24V

1

DB

2

SLD

3

FG

7

0V

NO.

ID

FUNCTION, NOTES

1

DB

----

2

SLD

Shield

3

FG

FG

4

DA

----

5

DG

----

6

+24V

Power input (24V DC)

7

0V

Power input (0V)

 

INPUT TERMINAL ASSIGNMENT

10

+IN0

11

–IN0

12

+IN1

1

+CJ0

2

–CJ0

3

+CJ1

13

–IN1

4

–CJ1

14

NC

5

NC

15

+IN2

6

+CJ2

16

–IN2

7

–CJ2

17

+IN3

8

+CJ3

9

–CJ3

18

–IN3

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

+CJ0 CJC 0

10 +IN0 T/C + 0

2

–CJ0 CJC 0

11 –IN0 T/C – 0

3

+CJ1 CJC 1

12 +IN1 T/C + 1

4

–CJ1 CJC 1

13 –IN1 T/C – 1

5

NC

No connection

14

NC

No connection

6

+CJ2 CJC 2

15 +IN2 T/C + 2

7

–CJ2 CJC 2

16 –IN2 T/C – 2

8

+CJ3 CJC 3

17 +IN3 T/C + 3

9

–CJ3 CJC 3

18 –IN3 T/C – 3

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7M-TS4-R

Страница 1: ...nted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices and connected wires may affect the protection level of this u...

Страница 2: ...0 bps 3 4800 bps EXTENSION MODULE Combinations with all extension modules are selectable OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Discrete i...

Страница 3: ...WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL mm inch Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Solder less ter...

Страница 4: ...ate both made of metal when installing the R7M Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielde...

Страница 5: ...d the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Страница 6: ...ons are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to th...

Страница 7: ...us Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To conn...

Отзывы: