• Configuration Properties
CONFIGURATION
PROPERTY
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
SCPTdirection
----
{SNVT_state}
{0 or 1}
{0,0,0,0,0,0,0,0,
0,0,0,0,0,0,0,0}
Bit 0 through 4: Counted object
0,0,0,0,0 : nviCNTIn
1,0,0,0,0 : ExX0
0,1,0,0,0 : ExX1
1,1,0,0,0 : ExX2
0,0,1,0,0 : ExX3
1,0,1,0,0 : ExX4
0,1,1,0,0 : ExX5
1,1,1,0,0 : ExX6
0,0,0,1,0 : ExX7
1,0,0,1,0 : ExX8
0,1,0,1,0 : ExX9
1,1,0,1,0 : ExXA
0,0,1,1,0 : ExXB
1,0,1,1,0 : ExXC
0,1,1,1,0 : ExXD
1,1,1,1,0 : ExXE
0,0,0,0,1 : ExXF
ExX0 through ExXF: Extension discrete input
Bit 6: Count function
0 : Number of status changes from OFF to ON
1 : Accumulated time of ON status
Bit 7: Memory storage at the non-volatile memory
0 : Count retained in the memory and preset at the startup
1 : Count always reset to 0
Bit 5, 8 through 15 : Invalid
Minimum input pulse width 500 ms for nviCNTIn, 50 ms
for the input terminals.
DO NOT connect a network variable to nviCNTIn when one
of the input terminals (other than nviCNTIn) is assigned as
the counted object.
ON time per 1 second increments.
SCPTinvrtOut
nviCNTIn
{SNVT_lev_disc}
{ST_OFF, ST_ON}
{ST_OFF}
Count logic at nviCNTIn.
ST_OFF : Count with nvoCNTIn = ON
ST_ON : Count with nvoCNTIn = OFF
SCPTpwrUpState
nviCNTCtrl
{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{100.0 1}
Set value applied at nviCNTCtrl when the power supply is
turned on.
0.0 0 : Stop counting
100.0 1 : Start counting
Invalid : Reset count value
SCPTnvType
nvoCNTOut
{SNVT_nv_type}
{}
{SNVT_count_32}
Indicates nvoCNTOut type.
For use with LonMaker and other tools.
SCPTmaxRnge
nvoCNTOut
Same as nvoCNTOut.
Default = Max. range value
available for the type
Maximum count for nvoCNTOut. Count reset to 0 and
restarted at overflow.
SCPTsetpoint
nvoCNTOut
Same as nvoCNTOut.
Default = Max. range value
available for the type
Set value applied at nvoCNTOut when fbCNT[ ] is Over-
Ride.