• Configuration Properties
CONFIGURATION
PROPERTY
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
SCPTnumDigits
nviARMIn
{SNVT_count}
{0,60...63,68...71}
{0}
Source of the input to nviARMIn
0 : LonMaker bound output network variable
60 : fbSV[0] nvoSVVal
61 : fbSV[1] nvoSVVal
62 : fbSV[2] nvoSVVal
63 : fbSV[3] nvoSVVal
68 : fbCV[0] nvoCVOut
69 : fbCV[1] nvoCVOut
70 : fbCV[2] nvoCVOut
71 : fbCV[3] nvoCVOut
Match nviARMIn network variable type to that of the
source when using 60...63 or 68...71.
SCPTnvType
nviARMIn
{SNVT_nv_type}
{}
{SNVT_lev_percent}
Indicates nviARMIn type.
For use with LonMaker and other tools.
SCPTsetpoint[0]
nviARMIn
{SNVT_lev_percent}
{-163.840...163.835}
{80.000}
{SNVT_temp}
{-274.0...6279.5}
{80.0}
{SNVT_temp_p}
{-273.17...327.66}
{80.00}
{SNVT_count_32}
{0...999 999 999}
{10 000}
Alarm 1 (nvoARM1) setpoint
SCPTsetpoint[1]
nviARMIn
{SNVT_lev_percent}
{-163.840...163.835}
{60.000}
{SNVT_temp}
{-274.0...6279.5}
{60.0}
{SNVT_temp_p}
{-273.17...327.66}
{60.00}
{SNVT_count_32}
{0...999 999 999}
{9 000}
Alarm 2 (nvoARM2) setpoint
SCPTsetpoint[2]
nviARMIn
{SNVT_lev_percent}
{-163.840...163.835}
{40.000}
{SNVT_temp}
{-274.0...6279.5}
{40.0}
{SNVT_temp_p}
{-273.17...327.66}
{40.00}
{SNVT_count_32}
{0...999 999 999}
{1 000}
Alarm 3 (nvoARM3) setpoint
SCPTsetpoint[3]
nviARMIn
{SNVT_lev_percent}
{-163.840...163.835}
{20.000}
{SNVT_temp}
{-274.0...6279.5}
{20.0}
{SNVT_temp_p}
{-273.17...327.66}
{20.00}
{SNVT_count_32}
{0...999 999 999}
{10}
Alarm 4 (nvoARM4) setpoint