FUNCTIONAL BLOCK: fbCNT[0...7]
fbCNT[0...7] (Object ID : 17...24)
nv 36
...nv 43
nviCNTIn
SNVT_switch
nv 44
...nv 51
nviCNTCtrl
SNVT_switch
nv 52
...nv 59
nvoCNTOut
SNVT_count_32
SNVT_count_f
Set the initial value at nviCNTCtrl at the startup
Set count logic (ON or OFF)
Set operating mode
Set network variable type nvoCNTOut
Set the maximum count
Set the value when fbCNT[ ] is reset
fbCNT[ ] :
SCPTdirection
nviCNTIn :
SCPTinvrtOut
nviCNTCtrl :
SCPTpwrUpState
nvoCNTOut :
SCPTnvType
SCPTmaxRnge
SCPTsetpoint
Network Variables
Configuration Properties
• Network Variables
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
nviCNTIn
{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
Counted object
nviCNTCtrl
{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
Controls operation of fbCNT
0.0 0 : Stop counting
100.0 1 : Start counting
Invalid : Reset count value
nvoCNTOut
{SNVT_count_32}
{0...999 999 999}
{0}
{SNVT_count_f}
{0...999 999}
{0}
Number of ON counts or accumulated time of ON status at nviCNTIn or
the input terminal