R7L-SV4
EM-7804-A Rev.5 P. 11 / 18
• Configuration Properties
CONFIGURATION
PROPERTY
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
SCPTnumDigits
nviCVIn
{SNVT_count}
{0,60...63}
{0}
Source of the input to nviCVIn
0 : LonMaker bound output network variable
60 : fbSV[0] nvoSVVal
61 : fbSV[1] nvoSVVal
62 : fbSV[2] nvoSVVal
63 : fbSV[3] nvoSVVal
Match nviCVIn network variable type to that of the source
when using 60...63.
SCPTnvType
nviCVIn
{SNVT_nv_type}
{}
{SNVT_temp}
Indicates nviCVIn type.
For use with LonMaker and other tools.
SCPTnvType
nvoCVOut
{SNVT_nv_type}
{}
{SNVT_temp}
Indicates nvoCVOut type.
For use with LonMaker and other tools.
SCPTsetpoint[0]
nviCVIn
Same as nviCVIn
Scaling setting
Output SCPTsetpoint[0] (nvoCVOut) is provided with the
input SCPTsetpoint[0] (nviCVIn).
Output SCPTsetpoint[1] (nvoCVOut) is provided with the
input SCPTsetpoint[1] (nviCVIn).
Output is proportionally provided to the input between
these setpoints.
SCPTsetpoint[0] < SCPTsetpoint[1]
SCPTsetpoint[1]
nviCVIn
Same as nviCVIn
SCPTsetpoint[0]
nvoCVOut
Same as nvoCVOut
SCPTsetpoint[1]
nvoCVOut
Same as nvoCVOut
056 222 38 18
www.sentronic.com
SENTRONIC
AG