R7L-SV4
EM-7804-A Rev.5 P. 14 / 18
SCPToffset
nviARMIn
{SNVT_lev_percent}
{0.000...163.835}
{5.000}
{SNVT_temp}
{0.0...6279.5}
{5.0}
{SNVT_temp_p}
{0.00...327.66}
{5.00}
{SNVT_count_32}
{0...999 999 999}
{50}
Alarm deadband (hysteresis)
■
FUNCTIONAL BLOCK: fbLED
fbLED (Object ID : 37)
nviLEDState
SNVT_state
nviLEDIn01
SNVT_switch
nviLEDIn02
SNVT_switch
nviLEDIn03
SNVT_switch
nviLEDIn16
SNVT_switch
Network Variables
Configuration Properties
nv 92
nv 93
nv 94
nv 95
nv 108
• Network Variables
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
nviLEDState
{SNVT_state}
{0 or 1}
{0,0,0,0,0,0,0,0,
0,0,0,0,0,0,0,0}
The front LEDs (0...F) turn on/off according to the input.
Bit 0 through Bit 15 assigned to LED 0 through F respectively.
DO NOT use nviLEDIn01...nviLEDIn16 when nviLEDState is used.
nviLEDIn01...
nviLEDIn16
{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
The front LEDs (0...F) turn on/off according to the input.
100.0 1 : LED ON
Other : LED OFF
DO NOT use nviLEDState when nviLEDIn01...nviLEDIn16 is used.
056 222 38 18
www.sentronic.com
SENTRONIC
AG