R7L-SV4
EM-7804-A Rev.5 P. 9 / 18
■
FUNCTIONAL BLOCK: fbSV[0...3]
fbSV [0...3] (Object ID : 25...28)
nvoSVVal
SNVT_lev_percent
Set input range
Deviation level to send
0% and 100% setpoints
Zero adjustment
Span adjustment
fbSV :
SCPTsceneNmbr
nvoSVVal :
SCPTsndDelta
SCPTsetpoint [ ]
SCPToffset
SCPTgain
Network Variables
Configuration Properties
nv 60
...nv 63
• Network Variables
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
nvoSVVal
{SNVT_lev_percent}
{-163.840...163.835}
{0.0}
% output proportional to the voltage/current at Input 0 through 3.
• Configuration Properties
CONFIGURATION
PROPERTY
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
SCPTsceneNmbr
----
{}
{0...11}
{0}
Input range for Input 0 through 3
0 : -10.00 to 10.00 V
1 : -5.00 to 5.00 V
2 : -1.00 to 1.00 V
3 : 0.00 to 10.00 V
4 : 0.00 to 5.00 V
5 : 1.00 to 5.00 V
6 : 0.00 to 1.00 V
7 : -0.500 to 0.500 V
8 : 0.000 to 0.500 V
9 : -20.00 to 20.00 mA
10 : 4.00 to 20.00 mA
11 : 0.00 to 20.00 mA
SCPTsndDelta
nvoSVVal
{SNVT_lev_cont}
{0.100...100.000}
{1.0}
Minimum deviation required to send out the network vari-
able.
SCPTsetpoint[0]
nvoSVVal
{SNVT_lev_percent}
{-15.000...115.000}
{0.0}
nvoSVVal lower range voltage/current in % of the input
range. SCPTsetpoint[0] < SCPTsetpoint[1]
SCPTsetpoint[1]
nvoSVVal
{SNVT_lev_percent}
{-15.000...115.000}
{100.000}
nvoSVVal upper range voltage/current in % of the input
range. SCPTsetpoint[0] < SCPTsetpoint[1]
SCPToffset
nvoSVVal
{SNVT_lev_percent}
{-163.840...163.835}
{0.0}
nvoSVVal zero (offset) adjustment.
Added to the calculation result with SCPTsetpoint[0,1] and
SCPTgain.
SCPTgain
nvoSVVal
{SNVT_muldiv
(mulplier,divisor)}
{0...32000,10000}
{10000,10000}
nvoSVVal span (gain) adjustment.
Gain = Multiplier / 10000 (Divisor is fixed at 10000.)
Applied to SCPTsetpoint[0,1].