R3-NC3

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8422  Rev.12  P. 7 / 7

 

PLC REDUNDANT SYSTEM (model: R3-NC3-x/W) 

Bit 0 of RY(n+1) is assigned to designate control system or standby system.  Set this bit from the host PLC to switch from the 
PLC master control system to the standby system, or vice versa.  The R3 module output (slave station) is controlled according 
to the bit combinations as shown in the table below.  No switching is required for the R3 input modules which continuously 
send out data to both ‘main’ and ‘sub’ network modules.
  RY(n+1) 0 = 0 : PLC master control system
  RY(n+1) 0 = 1 : PLC standby system

R3 MAIN (RY(n+1) 0)

R3 SUB (RY(n+1) 0)

CONTROL

0

0

Output from the ‘main’ network module.

0

1

Output from the ‘main’ network module.

1

0

Output from the ‘sub’ network module.

1

1

Hold the output

• Operation 

RY (n+1) 0 = 1

Communication Status

Start

Break

Restored

Switching by PLC

RY (n+1) 0 = 0

R3 main network

RY (n+1) 0 = 1

RY (n+1) 0 = 0

R3 sub network

(1)

(2)

(3)

(4)

(5)

1) When the PLC master control/standby system bit is undefined due to no communication, the both host PLCs function as 

‘standby’ system for each of R3 ‘main’ and ‘sub’ network modules.  All contact outputs are off, and analog output modules 

output -15%.

2) The master PLC communicates with the R3 main network module, while the standby PLC communicates with the R3 sub 

network module.

3) When a wire breakdown is detected at the R3 main network, the output signal is held for the preset time period (Timer is 

programmable with the PC Configurator Software, R3CON).  After the time has been elapsed, the output is switched from 

the R3 main to R3 sub network.  Be sure to set an appropriate output signal to the R3 sub network before the switching.  

The host PLC for the R3 main network is now functioning as standby system.

4) Once the PLC control is transferred to the standby system, it is necessary to set RY(n+1) 0 = 1 to the R3 main network in 

order to prevent R3 output control automatically switched to the main network when the R3 main network is restored.  If 

it is set to RY(n+1) 0 = 0, the R3 output will be switched to the main network even when the PLC control is in the standby 

system.

5) When both R3 main and R3 sub network modules are in communication, the output can be switched without delay by set-

ting RY(n+1) 0 values.  Be sure to set an appropriate output signal to the network module before the control is switched to 

it.

 

CONNECTION EXAMPLE for R3-NC3-x/W

Control

Main

R3-

NC3

I/O

Master

Master

CPU

R3-

NC3

Sub

Standby

R3-

NC3

I/O

Master

Master

CPU

R3-

NC3

Содержание R3-NC3

Страница 1: ...GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for maintenance without the power ENVIRONMENT Indoor use When heavy dust or metal parti...

Страница 2: ...as four types are to be occupied by each Two bits from SW1 and SW2 are assigned to each posi tion and data areas can be specified from the module No 1 through 8 Setting for No 9 and later modules is i...

Страница 3: ...EMC performance bond the FG terminal to ground Caution FG terminal is NOT a protective conductor terminal INTERNAL POWER INTERNAL BUS DG DB DA SLD FG To Other CC Link Devices CONFIGURATION JACK JACK...

Страница 4: ...to the network module 0 15 RWr n 0 2 4 6 8 10 12 14 Module 1 Module 2 Module 3 16 m 1 Module 4 Module 5 Module 6 Module 7 0 15 RWw n 0 2 4 6 8 10 12 14 Module 1 Module 2 Module 3 Module 4 Module 5 Mo...

Страница 5: ...R3 DA16A Power input in error or disconnected R3 YSx Output current error e g load unconnected Data Error Status RX n 2 0 through RX n 2 F indicate overrange R3 US4 out of 10 to 110 the other types ou...

Страница 6: ...plied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data For example 135 4 F is con verted into 135 Minus temper...

Страница 7: ...etwork modules All contact outputs are off and analog output modules output 15 2 The master PLC communicates with the R3 main network module while the standby PLC communicates with the R3 sub network...

Отзывы: