M-system R3-GE1 Скачать руководство пользователя страница 6

R3-GE1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8464  Rev.7  P. 6 / 7

Modbus I/O ASSIGNMENTS

ADDRESS

DATA TYPE

DATA

MODULE POSITION

Input (1X)

1025 – 1032

Module Status

Input Registers (3X)

1 – 16

I

Analog Input

1

17 – 32

2

33 – 48

3

49 – 64

4

65 – 80

5

81 – 96

6

97 – 112

7

113 – 128

8

257 – 288

F

Analog Input

1

289 – 320

2

321 – 352

3

353 – 384

4

385 – 416

5

417 – 448

6

449 – 480

7

481 – 512

8

Holding Registers (4X)

1 – 16

I

Analog Output

1

17 – 32

2

33 – 48

3

49 – 64

4

65 – 80

5

81 – 96

6

97 – 112

7

113 – 128

8

257 – 288

F

Analog Output

1

289 – 320

2

321 – 352

3

353 – 384

4

385 – 416

5

417 – 448

6

449 – 480

7

481 – 512

8

 

DATA TYPE

I: Integer, 0 – 10000 (0 – 100%)
F: Floating (32-bit data cannot be accessed via floating addresses.)

Note: DO NOT access addresses other than the ones mentioned above.  Such access may cause problems such as malfunction.

• Module Status

Module Status indicates whether individual I/O module is mounted or not.  The bit corresponding to the mounted slot turns 
to “1,” and the unmounted slot to “0.”

Содержание R3-GE1

Страница 1: ...it inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not apply physical impact to the unit Environmental temperature must be wi...

Страница 2: ...F OFF OFF 2 ON OFF OFF 3 OFF ON OFF 4 ON ON OFF 5 OFF OFF ON 6 ON OFF ON 7 OFF ON ON 8 ON ON ON LED Function SW3 4 Functions assigned to the front RUN and ERR LEDs can be selected SW3 4 LED FUNCTION R...

Страница 3: ...N DIAGRAM 1 4 Modbus TCP RJ 45 MODULAR JACK INTERNAL BUS INTERNAL POWER BUS CONNECTOR RUN RUN JACK RUN CONTACT OUTPUT CONFIGURATION JACK WIRING INSTRUCTIONS M3 SCREW TERMINAL Torque 0 5 N m SOLDERLESS...

Страница 4: ...ith 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sen...

Страница 5: ...ram Controller 14 Poll Controller 15 Force Multiple Coils X Digital output from the slave 16 Preset Multiple Registers X General purpose register within the slave 17 Report Slave ID Slave type RUN sta...

Страница 6: ...17 448 6 449 480 7 481 512 8 Holding Registers 4X 1 16 I Analog Output 1 17 32 2 33 48 3 49 64 4 65 80 5 81 96 6 97 112 7 113 128 8 257 288 F Analog Output 1 289 320 2 321 352 3 353 384 4 385 416 5 41...

Страница 7: ...l bus error occurs and the ERR LED turns on Max 16 real I O modules and virtual modules are available The interface module can not read the data for more than 16 modules WHEN R3 GE1 IS MOUNTED ON SLOT...

Отзывы: