TRANSMISSION DATA DESCRIPTIONS

Use the DIP SW located at the side of the module to specify expanded cyclic setting.  16 words input and 16 words output 
make 1 cyclic.  Max. 8 cyclic (128 words input, 128 words output) transmission is available.  1 cyclic is equivalent to 1 I/O 
module (analog input 16 points, analog output 16 points).  Max. 8 I/O modules can be assigned to 8 slots.

Note:  Do not mount any modules in the slots which are occupied by virtual modules.  If a real I/O module is mounted in the slot, an 

internal bus error occurs and the ERR LED turns on.  Max. 16 real I/O modules and virtual modules are available.   

 

The interface module can not read the data for more than 16 modules.

 

WHEN R3-GC1 IS MOUNTED ON SLOT NO. 2 (4 CYCLIC)

Real I/O modules are mounted on Slots No. 1 and 2, however, the network module (R3-NE1) recognizes that each of Slots No. 
1 to 5 is occupied.  That is, R3-NE1 recognizes R3-SV4 mounted on Slot No.1 as it is and recognizes R3-GC1 mounted on Slot 
No.2 as divided into four modules and occupying Slots No. 2 to 5.

SLOT

REAL MODULE VIRTUAL MODULE NO. OF WORDS

Slot No. 1

R3-SV4

R3-SV4

4 Words

Slot No. 2

R3-GC1

R3-GC1 (1/4)

16 Words

Slot No. 3

No module

R3-GC1 (2/4)

16 Words

Slot No. 4

No module

R3-GC1 (3/4)

16 Words

Slot No. 5

No module

R3-GC1 (4/4)

16 Words

Slot No. 6

No module

No module

----

Slot No. 7

R3-NE1

R3-NE1

----

Slot No. 8

R3-PS1

R3-PS1

----

 

OUTPUT DATA

The figure below shows the allocation of the data sent from 
the network module to the master.

 

INPUT DATA

The figure below shows the allocation of the data sent from 
the master to the network module.

0

15

RWrn

+

0

Module 1

+

15

+

31

0

F

0

15

E D C B A 9 8 7 6 5 4 3 2 1

RX(n

+

0)

Unused

Module Status

Reserved Bits

RX(n

+

7)

+

16*m

1

• The available data area for R3-GC1 is [16*m] (m=expanded cyclic setting)

CC-Link Ver.1.10

0

F

0

15

E D C B A 9 8 7 6 5 4 3 2 1

RX(n

+

0)

Unused

Module Status

Reserved Bits

RX(n

+

m*7

1)

CC-Link Ver.2.00

0

15

RWwn

+

0

+

15

+

31

+

16*m

1

Module 1

Module 2

Module 2

Module m

Module m

1

2

3

4

5

6

7

8

R3-

SV4

R3-BS08

R3-

GC1

R3-

NE1

R3-

PS1