• CC-Link Ver.1.10

1. Module Status
  RX (n + 0) 0 indicates whether a virtual I/O module is specified or not. 
  The virtual I/O module is a fixed one for CC-Link Ver.1.10, the related bit must be “1”.
     

RX (n + 0) 0  Virtual I/O module 1

2. RX (n + 1) to RX (n + 6) are not used.
3. RX (n + 7) 0 to RX (n + 7) 7 is a reservation area. 
  RX (n + 7) B is used as Ready signal, the bit is “1” when R3-GC1 is in normal.
  RX (n + 7) 8 to A, C to F are not used.

• CC-Link Ver.2.00

1. Module Status
  RX (n + 0) 0 to RX (n + 0) 7 indicates whether virtual I/O modules are specified or not. 
  When a virtual module is specified, the related bit is “1”.  When a virtual module is not specified, the related bit is “0”.
  The detailed information is as shown below.
     

RX (n + 0) 0  Virtual I/O module 1

     

RX (n + 0) 1  Virtual I/O module 2

     

RX (n + 0) 2  Virtual I/O module 3

     

RX (n + 0) 3  Virtual I/O module 4

     

RX (n + 0) 4  Virtual I/O module 5

     

RX (n + 0) 5  Virtual I/O module 6

     

RX (n + 0) 6  Virtual I/O module 7

     

RX (n + 0) 7  Virtual I/O module 8

2. RX (n + 1) to RX (n + m * 7 – 2) are not used.
3. RX (n + m * 7 – 1) 0 to RX (n + m * 7 – 1) 7 is a reservation area.
  RX (n + m * 7 – 1) B is used as Ready signal, the bit is “1” when R3-GC1 is in normal.
  RX (n + m * 7 – 1) 8 to A, C to F are not used.