background image

PSN1 / PSN3

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-4857  Rev.10  P. 6 / 9

PU-2x ADJUSTMENTS

 

DISPLAY

G

ITEM No.

I

(

)

D

Response Messages

Data to be entered

or Messages

LCD Display

• Response Messages

  NG:  No good
     

The PU-2x may not be securely connected.

     

Check connection of the modular jack.

  ER:  Communication error
     

Turn the SW-8 ON.

• Data Indicator

  OK: OK
  DATA-ERR: Invalid data input
  NON-ITEM: ITEM No. not applicable

 

PROGRAMMABLE ITEMS

Table 4. Programmable items                           (    ) for PSN3

ITEM

No.

ITEM

USABLE

RANGE

MINIMUM

INCREMENT

DEFAULT

10

Full-open/-closed
position (retracted)

8 – 100

0.1

100

11

Full-open/-closed
position (extended)

0 – 92

0.1

0

12

Retracted side limit

75 – 105

0.1

100

13

Extended side limit

-5 – 25

0.1

0

14

Full-open/-closed 
output (retracted)

75 – 100

0.1

98

15

Full-open/-closed
output (extended)

0 – 25

0.1

2

16

Split ON/OFF

0 or 1

0

17

Split type LO/HI

0 or 1

0

18

Split point

30 – 70

0.1

50

19

Opening/closing
speed limit

1 – 50

1

16 (24)

20

Deadband

0.1 – 5

0.1

0.5

21

Restart limiting timer

0 – 30*

2

0.1*

2

2

22

Speed in shutdown*

3

1 – 50

1

16 (24)

23

Position in shutdown*

3

0 – 100

0.1

    0

*2. ROM version 1.05 or later
*3. Settings are enabled with ‘Failsafe’ option.

 

ROM VERSION INDICATION

Press ITEM 99 in the local calibration mode in order to dis-
play the ROM version of the PSN.

 

HOW TO PROGRAM THE PSN

1) Apply power supply voltage to the PSN.
2) Turn ON the SW-8 in order to put the PSN in the local 

calibration mode, and the input signal is disregarded.

3) Connect the modular jack cord of the PU-2x to the PSN.
  ITEM display is blank.
4) Indicating Current Setting
  Key in the ITEM No. that you want to check. (N = 0 to 9)
  Press [ITEM]  [N]  [N].

5) Indicating New ITEM No.
  Press [ITEM]  [N]  [N] or press [UP] or [DOWN].
6) Modifying Current Setting
  Display the ITEM No. that you want to change, and press 

[DATA], new setting, and [ENTER].

  If an irrelevant setting is entered, the PU-2x indicates 

“DATA-ERR” on its message display.  Key in an appropri-

ate setting again.

7) Remove the modular jack cord of the PU-2x.
8) Turn OFF the SW-8 in order to return the PSN in the 

operating mode.  Apply input signals and confirm every 

setting.

Note 1:  DO NOT remove power to the PSN with the PU-2x 

connected to it.

Note 2:  Be sure to remove the PU-2x before driving the motor 

(in the operating mode).

 

EXPLANATIONS ABOUT THE PROGRAMMABLE ITEMS

1) Full-Open/-Closed Positions (ITEM No.10, 11)
  Key in a percentage value within 0% for the extended 

end, and 100% for the retracted end.

  [Extended End] > [Retracted End]
2) Extended/Retracted Limits (ITEM No.12, 13)
  The adjustable ranges shown in Table 4 are applicable 

against the stroke determined by the full-open/-closed 

positions as 100%.

3) Full-Open/-Closed Outputs (ITEM No.14, 15)
  The adjustable ranges shown in Table 4 are applicable 

against the stroke determined by the full-open/-closed 

positions as 100%.

4) Split Range (ITEM No.16 to 18)
  Refer to Figure 9 and determine the type and point of 

split range.

  When the split range is set to OFF (ITEM No.16), the 

split range type and point (ITEM No.17, 18) are invalid.

0

Adjustable Split Point Range

100%

50

30

70

Retracted End

Extended End

Split Range Type Set to “LO”
(Set to “DIRECT” Action)

Split Range Type Set to “HI”
   (Set to “REVERSE” Action)

Thick, solid lines indicate 

examples of I/O characteristics, 

while broken lines indicate 

limits of adjustable range.

INPUT (%)

OUTPUT STEM

POSITION

Figure 9.  Split Range

Содержание PSN1

Страница 1: ...outdoor or where it is exposed to rain or water drops adequate precaution must be done for preventing water from entering inside through wiring conduits It could cause electric shock DO NOT mount the...

Страница 2: ...lding If outside keep away from direct sun light Operating temperature 25 to 55 C 13 to 131 F for PSN1 15 to 55 C 5 to 131 F for PSN3 Operating humidity 30 to 85 RH non condensing Vibration 2 G 19 6 m...

Страница 3: ...1 OPEN CLOSE SIGNAL RETRACTED OPEN CLOSE SIGNAL EXTENDED ALARM 10 9 8 7 6 5 1 2 POWER V U POWER INPUT ALARM DOWN EXTEND UP RETRACT 1 EXTEND RETRACT 2 ACCORDING TO SW1 STOP 3 REVERSE DIRECT 4 5 RETRACT...

Страница 4: ...he opening equals the value 5 Fix both stems with a lock nut 6 Apply power input and approx 50 input signal and check that there is no opening between the yoke and valve bonnet Fix the yoke and the va...

Страница 5: ...ing input Valve stem pushed in In DIRECT action the input signal 0 100 corresponds to the position output signal 20 4mA DC FULL OPEN CLOSED POSITIONS 1 Turn ON the SW 8 in order to put the PSN in the...

Страница 6: ...nk 4 Indicating Current Setting Key in the ITEM No that you want to check N 0 to 9 Press ITEM N N 5 Indicating New ITEM No Press ITEM N N or press UP or DOWN 6 Modifying Current Setting Display the IT...

Страница 7: ...20 10 30 40 50 0 500 1000 1500 2000 2500 3000 3500 0 1 2 3 4 5 6 7 THRUST N SPEED mm s SPEED SCALE Thrust Speed Figure 10 PSN1 Speed v s Thrust 0 20 10 30 40 50 0 1000 2000 3000 4000 5000 6000 0 1 2...

Страница 8: ...e is blown quickly it is possible that the control PCB and or motor are damaged Consult M Sys tem or M System s representative MOTOR PREHEAT FUNCTION When the PSN detects a temperature lower than 0 C...

Страница 9: ...voltage or input signal Remove the causes of malfunction and secure the signals Unstable functioning Operating speed is too fast Secure the required thrust by slowing Power voltage is too low or fluct...

Отзывы: