background image

PSN1 / PSN3

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-4857  Rev.10  P. 2 / 9

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• This equipment is suitable for Pollution Degree 2 and  

Installation Category II (transient voltage 2500V).  Re-
inforced insulation (Signal or metallic housing or seq. 
signals or battery status (with failsafe function only) to 
power: 300V) is maintained.  Prior to installation, check 
that the insulation class of this unit satisfies the system 
requirements.

• Altitude up to 2000 meters.
• The equipment must be installed such that appropriate 

clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• Install lightning surge protectors for those wires connect-

ed to remote location.  Refer to “LIGHTNING SURGE 
PROTECTION” section below.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  100 – 120V AC rating: 90 – 132V, 47 – 66 Hz, 
     

 

 

 

      approx. 240VA (200VA for PSN3)

  200 – 240V AC rating: 180 – 264V, 47 – 66 Hz, 
     

 

 

 

      approx. 240VA (200VA for PSN3)

  24V DC rating: 24V ±10%, approx. 3A

 

GENERAL PRECAUTIONS

• DO NOT install signal wires and power supply wires to-

gether in one duct because it may cause a malfunction 
due to inductive noises.  If they must be installed togeth-
er, use shielded cables.

• If input signals are to be turned on/off with power sup-

plied to the actuator, be sure to set the abnormal low in-
put operation mode.

 

ENVIRONMENT

• Inside building.  If outside, keep away from direct sun-

light.

• Operating temperature -25 to +55°C (-13 to +131°F) for 

PSN1; -15 to +55°C (5 to 131°F) for PSN3.

• Operating humidity 30 to 85% RH (non-condensing)
• Vibration 2 G  (19.6 m/s

2

) max.

• The actuator must be installed in a place where mainte-

nance and inspection can be conducted.  Observe at least 
15 cm (5.9 in.) of open space at the top of its cover for 
maintenance and inspection.

• Keep away from hazardous atmosphere such like explo-

sive or corrosive gases.

 

SOUND ACCOMPANYING MOTOR ROTATION

• The PSN’s stepping motor inherently generates whistling 

sound during normal operation according to its rotating 
frequency, larger with lower frequencies.  DO NOT be 
alarmed.

 

PID CONTROL SIGNAL

• Choose PID parameters carefully so that the MV remains 

as stable as possible.  Unstable control shortens the life of 
actuator and valve.

 

GASKET

• Be sure to return the gasket when you close the cover 

after wiring or adjustments.

 

SCREW TORQUE

• The torque for tightening screws for the cover is between 

2.4 – 3.1 N·m (1.8 – 2.3 ft·lb).

 

DESIGNING YOKE

• When a foreign object is caught in the valve, a thrust as 

great as 7500 N (1686 lb) could be applied to the yoke.  
Observe enough strength when designing mechanical 
components such like the yoke.

• When the PSN is used on a steam stream in temperature 

control, its temperature may rise beyond ambient tem-
perature caused by a heat conducted or radiated from pip-
ing.  Use a longer yoke for effective heat dissipation and 
apply insulation material.

 

OPERATING CONDITION

• Depending on operating condition, internal temperature 

may rise extremely high.

• When operating continuously with such a condition, it 

causes short life span or damage and may impair expect-
ed performance.

• Operate with an enough margin such as shortening the 

operational duty time ratio.

Содержание PSN1

Страница 1: ...outdoor or where it is exposed to rain or water drops adequate precaution must be done for preventing water from entering inside through wiring conduits It could cause electric shock DO NOT mount the...

Страница 2: ...lding If outside keep away from direct sun light Operating temperature 25 to 55 C 13 to 131 F for PSN1 15 to 55 C 5 to 131 F for PSN3 Operating humidity 30 to 85 RH non condensing Vibration 2 G 19 6 m...

Страница 3: ...1 OPEN CLOSE SIGNAL RETRACTED OPEN CLOSE SIGNAL EXTENDED ALARM 10 9 8 7 6 5 1 2 POWER V U POWER INPUT ALARM DOWN EXTEND UP RETRACT 1 EXTEND RETRACT 2 ACCORDING TO SW1 STOP 3 REVERSE DIRECT 4 5 RETRACT...

Страница 4: ...he opening equals the value 5 Fix both stems with a lock nut 6 Apply power input and approx 50 input signal and check that there is no opening between the yoke and valve bonnet Fix the yoke and the va...

Страница 5: ...ing input Valve stem pushed in In DIRECT action the input signal 0 100 corresponds to the position output signal 20 4mA DC FULL OPEN CLOSED POSITIONS 1 Turn ON the SW 8 in order to put the PSN in the...

Страница 6: ...nk 4 Indicating Current Setting Key in the ITEM No that you want to check N 0 to 9 Press ITEM N N 5 Indicating New ITEM No Press ITEM N N or press UP or DOWN 6 Modifying Current Setting Display the IT...

Страница 7: ...20 10 30 40 50 0 500 1000 1500 2000 2500 3000 3500 0 1 2 3 4 5 6 7 THRUST N SPEED mm s SPEED SCALE Thrust Speed Figure 10 PSN1 Speed v s Thrust 0 20 10 30 40 50 0 1000 2000 3000 4000 5000 6000 0 1 2...

Страница 8: ...e is blown quickly it is possible that the control PCB and or motor are damaged Consult M Sys tem or M System s representative MOTOR PREHEAT FUNCTION When the PSN detects a temperature lower than 0 C...

Страница 9: ...voltage or input signal Remove the causes of malfunction and secure the signals Unstable functioning Operating speed is too fast Secure the required thrust by slowing Power voltage is too low or fluct...

Отзывы: