MODBUS FUNCTION CODES & SUPPORTED CODES

 

COMMUNICATION PARAMETERS

PARAMETERS

SPECIFICATIONS

DEFAULT

MODIFICATION

Data Mode

RTU

RTU

Not modifiable

Baud Rate

9600 / 19200 / 38400 bps

38400 bps

JXCON Software

Parity

None / Odd / Even

Odd

JXCON Software

Bit Length

8

8

Not modifiable

Stop Bit

1

1

Not modifiable

Node Addresses

1 to 247

1

Hardware Rotary SW for 1 through 15,
JXCON Software for 16 through 247 (Rotary SW set to 
0).

Floating Point Data

Normal / Swapped

Normal

JXCON Software

Physical Layer

RS-485

RS-485

Not modifiable

 

FUNCTION CODES

CODE

NAME

*

1

NOTES

01 (0x01)

Read Coil Status

Reading DO

02 (0x02)

Read Input Status

Reading DI

03 (0x03)

Read Holding Register

04 (0x04)

Read Input Register

05 (0x05)

Force Single Coil

Writing single DO

06 (0x06)

Preset Single Register

15 (0x0F)

Force Multiple Coils

Writing multiple DO

16 (0x10)

Force Multiple Registers

*1. Based upon Modbus Protocol Reference Guide PI-MBUS-300

 

DATA ADDRESS

ADDRESS

DATA FORMAT

NAME

Coil (0X)

1 – 16

DO (internal switch)

17

Operation Mode SW (0 : Programming Mode, 1 : Run Mode)

18

Cold junction compensation SW (0 : Disable, 1 : Enable)*

2

19

Linearization SW (0 : Disable, 1 : Enable)*

3

23

Remote output mode SW (0 : Local, 1 : Remote)

Input Status (1X)

1 – 16

DI (internal switch)

17

Input data error (0 : Normal, 1 : Error)

Input Register (3X)

1 – 2

F

AI in %

3 – 4

F

AI in engineering unit

5 – 6

F

Cold junction temperature (°C, °F or K)*

2

7

I

AI in % *

4

8

I

Bit

Status Description

0 – 3
4
5
6
6
8 – 15

Reserved for system’s use
1 : ADC Channel 1 Overrange
1 : ADC Channel 2 Overrange
1 : Burnout Detected
1 : ADC Hardware Error Detected
Reserved for system’s use

129 – 144

B16

Model No. “M2XUM”

Holding Register (4X)

1 – 2

F

AO in % *

5

3

I

AO in % *

4,

 *

5

4

I

Input type No. *

6

5

I

Temperature unit (3 : °C, 4 : °F, 5 : K) *

7

6

I

Burnout type (0 : No Burnout, 1 : Downscale, 2: Upscale)

7

I

(Reserved)

8

I

#1 output type No. (0 : 0 – 20mA, 1 : ±2.5V, 2 : ±10V) *

6

9 – 10

I

(Reserved, integer)

17 – 18

F

Input 100% scaled value

19 – 20

F

Input 0% scaled value

21 – 22

F

Output 100% scaled value (V or A)

23 – 24

F

Output 0% scaled value (V or A)

25 – 28

F

(Reserved, 32-bit floating)

29 – 33

B10

Tag No.

I = 16-bit integer, F = 32-bit floating, Bn = n-byte character
*2. Thermocouple input     *3. DC and Potentiometer input     *4.  0 – 100% converted into 0 – 20000
*5. Remote Output Mode SW automatically turned ON when reading
*6. Be sure to scale 0% and 100% after the input type has been changed.     *7. Thermocouple and RTD input