EM-5009 Rev.8 P. 6 / 6
■
INPUT TYPE & RANGE
I/O
I/O TYPE
SELECTION
USABLE RANGE
DC input
0
0 – 50 mA
0 – 50 mA
1
-1 – +1 V
-1 – +1 V
2
-10 – +10 V
-10 – +10 V
T/C input
16
(PR)
0 – 1760°C
17
K (CA)
-270 – +1370°C
18
E (CRC)
-270 – +1000°C
19
J (IC)
-210 – +1200°C
20
T (CC)
-270 – +400°C
21
B (RH)
0 – 1820°C
22
R
-50 – +1760°C
23
S
-50 – +1760°C
24
C (WRe 5-26)
0 – 2315°C
25
N
-270 – +1300°C
26
U
-200 – +400°C
27
L
-200 – +900°C
28
P (Platinel II)
0 – 1395°C
29
User’s T/C
RTD input
32
JPt 100 (JIS ’89)
-200 – +500°C
33
Pt 100 (JIS ’89)
-200 – +850°C
34
Pt 100 (JIS ’97, IEC)
-200 – +850°C
35
Pt 50 Ω (JIS ’81)
-200 – +649°C
36
Ni 508.4 Ω
-50 – +200°C
37
Pt 1000
-200 – +200°C
38
Ni 100
-50 – +200°C
39
Cu 10 @ 25°C
-50 – +200°C
40
User’s RTD
POT input
48
0 – 100 ohms
0 – 100 %
49
0 – 300 ohms
0 – 100 %
50
0 – 1 k ohms
0 – 100 %
51
0 – 10 k ohms
0 – 100 %
Note: Be sure to scale 0% and 100% input after the input type No. has been changed.