background image

M3LLC

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-2654  Rev.17  P. 6 / 8

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  DIP SW setting:  Check that the switches are set to ap-

propriate positions.

3) Power input voltage:  Check voltage across the terminal 

11 – 12 with a multimeter.

4) Input:  Check that the input signal is within 0 – 100% of 

full-scale.

5) Output:  Check that the load resistance meets the de-

scribed specifications.

I/O RANGING & FINE ADJUSTMENTS

After the DIP SW setting is complete, set up the precise 
input and output range using the front control buttons.  Be 
sure that the front control button function is enabled with 
the DIP switch setting.
The front LEDs’ colors and blinking patterns help you to 
easily identify the transmitter’s status and confirm the set-
up actions in each step of Calibration Modes.  Please read 
the following explanations referring to “Calibration Flow 
Chart”.

 

PREPARATION

1) Mount the DIP-SW-configured M3LLC on to a DIN rail.
2) Connect the M3LLC to a simulator and a multimeter and 

to a power source as shown below.

3) Turn the power supply on and wait for 10 minutes.

1

2

7

8

11

12

M3LLC

Multimeter

Simulator

Shortcircuit

+

Power Source

+ –

+

5

 

INPUT & OUTPUT RANGING

[Example] Setting input to 0 – 10 mV, output to 1 – 5 V DC

1) Run Mode: Confirm that the green LED is blinking 

(model M3LLC-x-x/A) or the green LED turns on (model 

M3LLC-x-x/B).

2) Input Ranging Mode: Hold down MODE button for longer 

than 5 seconds until the LD1 red LED is ON and the LD2 

red LED is blinking.

3) 0% Input Ranging: Apply the desired minimum input lev-

el (e.g. 0 mV) from the simulator and hold down DOWN 

button until the LD1 blinks for approx. 2 sec. and then 

turns OFF.  When you release the button, the LD1 is re-

turned to ON.

  The blinking LD1 means that the value is stored in the 

memory.  If LED’s blinking frequency does not change, 

the entered level may be inappropriate:  too small a span, 

or out of usable range (same for all steps).

4) 100% Input Ranging: Apply the desired maximum input 

level (e.g. 10 mV) from the simulator and hold down UP 

button until the LD1 blinks for approx. 2 sec. and then 

turns OFF.  When you release the button, the LD1 is re-

turned to ON.

5) Output Ranging Mode: Press MODE button and confirm 

that the LD1 red LED is ON and the LD3 red LED in-

stead of LD2 is blinking.

6) 0% Output Ranging: Increase or decrease the simulated 

input until the meter shows the desired minimum output 

level (e.g. 1 V).  Hold down DOWN button until the LD1 

blinks for approx. 2 sec. and then turns OFF.  When you 

release the button, the LD1 is returned to ON.

7) 100% Output Ranging: Increase or decrease the simu-

lated input until the meter shows the desired maximum 

output level (e.g. 5 V).  Hold down UP button until the 

LD1 blinks for approx. 2 sec. and then turns OFF.  When 

you release the button, the LD1 is returned to ON.

8) Run Mode: When calibration is completed, press MODE 

button once and confirm that: the LD1 green LED is 

blinking in case of M3LLC-x-x/A; and the LD1 green LED 

is ON in case of M3LLC-x-x/B.

 

ZERO & SPAN ADJUSTMENTS

After the transmitter is installed and operational, fine zero 
and span tuning can be performed as explained below.  Both 
zero and span are adjustable within ±15%.

1) Run Mode: Confirm that the green LED is blinking 

(model M3LLC-x-x/A) or the green LED turns on (model 

M3LLC-x-x/B).

2) Fine Zero Adjustment Mode: Hold down MODE button 

for 1 or 2 seconds until the LD1 red LED is ON and the 

LD2 green LED is blinking.

  Use UP (increase) and DOWN (decrease) buttons to ad-

just the output to 0%.

3) Fine Span Adjustment Mode: Press MODE button and 

confirm that the LD1 red LED is ON and the LD3 green 

LED instead of LD2 is blinking.

  Use UP (increase) and DOWN (decrease) buttons to ad-

just the output to 100%.

4) Run Mode: When fine adjustment is completed, press 

MODE button once and confirm that: the LD1 green LED 

is blinking in case of M3LLC-x-x/A; and the LD1 green 

LED is ON in case of M3LLC-x-x/B.

Note 1:  Calibration steps can be skipped when not needed by 

repeating pushing MODE buttons.

Note 2:  There is no limitation of entering values for multiple 

times within one step of Calibration Mode.  Signal 
level is stored each time the respective UP or DOWN 
button is pressed.  However, for the input ranging, end 
always with 100% (UP).

 

TARE ADJUSTMENT

1) Apply tare load to the sensor.
2) Close across the tare command input terminals.  Tare ad-

justment value is set so that present sensor input value 

equals input 0%.

3) Open the tare command input terminals.

Note:  When input calibration or ranging is performed, tare 

adjustment value is reset to 0% automatically.  Perform 
the tare adjustment again.

Содержание M3LLC

Страница 1: ...urations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole...

Страница 2: ...where the housing cover is latched The plastic housing may be damaged HOW TO SEPARATE THE EURO TYPE CONNECTOR TERMINAL BLOCKS When you need to separate the euro type connector termi nal blocks from th...

Страница 3: ...RAM CONFIGURATOR JACK 7 8 11 12 OUTPUT POWER 1 4 5 2 3 STRAIN GAUGE 6 INPUT EXC TARE COMMAND INPUT Di WIRING INSTRUCTIONS Applicable wire size Solid 0 2 to 2 5 mm2 0 55 to 1 75 dia Stranded 0 2 to 2 5...

Страница 4: ...Excitation Adj Rotary SW 10 11 12 7 8 9 4 5 6 1 2 3 Configurator Jack DOWN Button UP Button MODE Button LED3 LD3 LED2 LD2 LED1 LD1 FRONT VIEW SIDE VIEW 1 SW3 SW1 2 3 4 5 6 7 8 OFF ON OFF ON 1 2 3 4 S...

Страница 5: ...be set up on a PC regardless of other DIP SW setting except for the output type must be selected with the DIP SW1 1 through SW1 4 See Table 6 For detailed information on the PC configuration refer to...

Страница 6: ...e button the LD1 is re turned to ON 5 Output Ranging Mode Press MODE button and confirm that the LD1 red LED is ON and the LD3 red LED in stead of LD2 is blinking 6 0 Output Ranging Increase or decrea...

Страница 7: ...G R R R R G R R G Fine Adjustments I O Ranging HOLD DOWN MODE 1 2 s HOLD DOWN MODE 5s PRESS MODE PRESS MODE PRESS MODE PRESS MODE HOLD DOWN DOWN HOLD DOWN UP DOWN UP MODE HOLD DOWN DOWN HOLD DOWN UP...

Страница 8: ...tes the CPU s communication error DIP SW Error DIP SW configuration is inappropriate Check the DIP SW setting referring to Tables 2 6 Input Saturated in PC Configuration Mode Option A The input is sat...

Отзывы: