EM-2654 Rev.17 P. 7 / 8
■
I/O RANGE LABEL
Blank I/O range labels are included in the product package.
Write in the configured ranges and put the label on the side
as shown below.
INPUT
OUTPUT
I/O Range Label (included in the product package)
■
CALIBRATION FLOW CHART
POWER ON
Amber LED
Green LED
Control
Buttons
Red LED
OFF
ON
Blink
RUN MODE
LD2
LD3
A
G
RUN MODE
LD2
LD3
G
R
LD1
LD2
LD3
LD1
LD2
LD3
0% INPUT
CONFIGURED
100% INPUT
CONFIGURED
INPUT
RANGING
MODE
LD1
OUTPUT
RANGING
MODE
LD2
LD3
LD1
LD2
LD3
0% OUTPUT
CONFIGURED
100% OUTPUT
CONFIGURED
G
G
R
R
R
R
G
R
R
G
Fine Adjustments ?
I/O Ranging ?
HOLD DOWN
MODE
1 – 2 s
HOLD DOWN
MODE
> 5s
PRESS
MODE
PRESS
MODE
PRESS
MODE
PRESS
MODE
HOLD DOWN
DOWN
HOLD DOWN
UP
DOWN
UP
MODE
HOLD DOWN
DOWN
HOLD DOWN
UP
When you set 0% or 100% input/output ranges,
keep pressing UP or DOWN button until the
LD1 blinks for approx. 2 seconds and turns off,
which indicates the setup is complete.
If LED’s blinking frequency does not change,
the entered level may be inappropriate: e.g. out
of usable range.
*
For the model M3LLC-x-x/A, the green LED is blinking.
For the model M3LLC-x-x/B, the green LED turns on.
FINE ZERO
ADJUSTMENT MODE
UP
or
DOWN
FINE SPAN
ADJUSTMENT MODE
UP
or
DOWN
Apply simulated 0% input signal.
Apply simulated 100% input signal.
Adjust simulated input until the output meter
shows desired 0% output.
Adjust simulated input until the output meter
shows desired 100% output.
LD1
*
LD1
*