M2EXS
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax:
+81(6)6659-8510 E-mail: [email protected]
EM-5137-B Rev.1 P. 8 / 18
•
Parameters
MODE
ITEM SETTING PARAMETER
RANGE
UNIT
INITIAL VALUE
Basic setting
01
Lockout setting
Lock / Unlock
—
Lock
06
Angle offset
—
Deg.
0.00
07
Angle span
60.00 – 359.99
Deg.
270.00
10
Rotating direction
CW/CCW
—
CW
14
0 % input scaling
-99999 – 999999
—
0.00
15
100 % input scaling
-99999 – 999999
—
100.00
16
Input decimal point
No decimal point
The number of decimal places : 1 – 5
—
2 places of decimals
17
Output range
0 – 20mA
-5 – +5V
-10 – +10V
—
0 – 20mA
18
0 % output setting
0.000 – 19.000
-5.000 – 4.750
-10.000 – 9.000
mA
V
V
4.000
19
100 % output setting
1.000 – 20.000
-4.750 – 5.000
-9.000 – 10.000
mA
V
V
20.000
20
0 % output scaling
-99999 – 999999
—
0.00
21
100 % output scaling
-99999 – 999999
—
100.00
22
Output decimal point
No decimal point
The number of decimal places : 1 – 5
—
2 places of decimals
23
Overrange output < 0%
-5.00 – 0.00
%
-5.00
24
Overrange output > 100% 100.00 – 105.00
%
105.00
26
Loop test
-5.00 – 105.00
%
Cancel