[01] Lockout setting

Set Lock / Unlock of lockout setting.

SETTING VALUE DESCRIPTION

INITIAL VALUE

Lock

Lockout setting enable

Lock

Unlock

Lockout setting disable

Even when setting is ‘Lock’, it is available to move on to 

each setting mode and confirm the setting value of each 

setting parameter. In each setting parameter display, when 

‘Lock’, ‘DATA (Locked)’ is indicated, when ‘Unlock’, ‘DATA’ 

is indicated.

[06] Angle offset

Set the position for 0% input entered to the unit.  Setting 

is performed by teach.  Press set button to display the pre-

sent input value.  With input value desired as 0% is entered, 

pressing set button again enables to fix the setting.  The 

value entered the setting is displayed as ‘INPUT’ in meas-

uring mode.

[07] Angle span

Set the Angle span.

SETTING RANGE

INITIAL VALUE

60 – 359.99

270.00

[10] Rotating direction

Set the rotating direction of input value.

SETTING VALUE

DESCRIPTION

CW

Clockwise

CCW

Counter-clockwise

[14] 0 % input scaling

Set the display value of 0 % input.

SETTING RANGE

INITIAL VALUE

-99999 – 999999

0

[15] 100 % input scaling

Set the display value of 100 % input.

SETTING RANGE

INITIAL VALUE

-99999 – 999999

100.00

[16] Input decimal point

Set the decimal point position of [14] 0 % and [15] 100 % 

input scaling. 

SETTING VALUE DESCRIPTION

INITIAL VALUE

oooooo

Decimal point: None

2 places of deci-
mals

ooooo.o

Number of decimal places: 1

oooo.oo

Number of decimal places: 2

ooo.ooo

Number of decimal places: 3

oo.oooo

Number of decimal places: 4

o.ooooo

Number of decimal places: 5

[17] Output range

Set the range of output signal of the unit.

SETTING VALUE DESCRIPTION

INITIAL VALUE

0 – 20 mA

Output: 0 – 20 mA DC

0 – 20 mA

-5 – +5 V

Output: -5 – +5 V DC

-10 – +10 V

Output: -10 – +10 V DC

When output range is changed, turn the power off, and 

then set the output setting DIP SW on the side of the unit.  

Setting is as follows.  Output setting value is changed to ini-

tial value.

OUTPUT 

RANGE

SW1

1

2

3

4

5

6

7

8

0 – 20 mA

OFF ON OFF OFF OFF OFF ON OFF

-

5 – +5 V

OFF OFF ON OFF ON OFF OFF ON

-

10 – +10 V

OFF OFF ON OFF OFF ON OFF ON

[18] 0 % output setting

Set the 0 % output setting.

OUTPUT RANGE SETTING RANGE MIN. SPAN INITIAL VALUE

0 – 20 mA

0.000 – 19.000

1.000

 4.000

-5 – +5 V

-5.000 – 4.750

0.250

-5.000

-10 – +10 V

-10.000 – 9.000

1.000

-10.000

Set as follows.
[18] 0 % output setting < [19] 100 % output setting
The value is indicated by ‘OUTPUT’ at measuring mode.

[19] 100 % output setting

Set the 100 % output setting.

OUTPUT RANGE SETTING RANGE MIN. SPAN INITIAL VALUE

0 – 20 mA

1.000 – 20.000

1.000

20.000

-5 – +5 V

-4.750 – 5.000

0.250

5.000

-10 – +10 V

-9.000 – 10.000

1.000

10.000

Set as follows.
[18] 0 % output setting < [19] 100 % output setting
The value is indicated by ‘OUTPUT’ at measuring mode.

[20] 0 % output scaling

Set the display value of [18] 0 % output setting.

SETTING RANGE

INITIAL VALUE

-99999 – 999999

0.00

[21] 100 % output scaling

Set the display value of [19] 100 % output setting.

SETTING RANGE

INITIAL VALUE

-99999 – 999999

100.00 

[22] Output decimal point

Set decimal point position for [20] 0 % and [21] 100 % out-
put scaling.

SETTING VALUE DESCRIPTION

INITIAL VALUE

oooooo

Decimal point: None

2 places of deci-
mals

ooooo.o

Number of decimal places: 1

oooo.oo

Number of decimal places: 2

ooo.ooo

Number of decimal places: 3

oo.oooo

Number of decimal places: 4

o.ooooo

Number of decimal places: 5

[23] Overrange output <0 %

Set the output range for not greater than 0 %. 
Available range between -5.00 to 0.00 %.

[24] Overrange output >100 %

Set the output range for not less than 100 %. 
Available range between 100.00 to 105.00 %.

Содержание M2EXS

Страница 1: ...f this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity...

Страница 2: ...ving the socket push down the DIN rail adaptor utilizing a minus screwdriver and pull WALL MOUNTING Refer to the drawings in the shown below TERMINAL CONNECTIONS Connect the unit as in the diagram bel...

Страница 3: ...ing changeable state used to enter save the setting value Used to move on through digits of setting value for input output scaling at setting changeable state Up Button Used to shift through setting p...

Страница 4: ...tting of the Advanced mode for settings DISPLAY IN EACH SETTING MODE For each setting current values of setting parameter ITEM number and setting value are indicated During setting Setting is indicate...

Страница 5: ...RT POWER ON Measuring Mode Hold down Mode Button for 2 seconds Hold down Mode Button for 2 seconds Basic Setting Mode Option Mode Advanced Mode Hold down Mode Button for 2 seconds Hold down Mode Butto...

Страница 6: ...ing value to set value Keeping pressing Down button enables to decrease the value continuously Operation of input setting parameter 06 Angle offset is set by teach The present input value is displayed...

Страница 7: ...ds Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Do...

Страница 8: ...input scaling 99999 999999 100 00 16 Input decimal point No decimal point The number of decimal places 1 5 2 places of decimals 17 Output range 0 20mA 5 5V 10 10V 0 20mA 18 0 output setting 0 000 19 0...

Страница 9: ...the unit SETTING VALUE DESCRIPTION INITIAL VALUE 0 20 mA Output 0 20 mA DC 0 20 mA 5 5 V Output 5 5 V DC 10 10 V Output 10 10 V DC When output range is changed turn the power off and then set the outp...

Страница 10: ...ase it by pressing Up and Down button Press and hold them enables to change value continuously 1 Pressing and holding Mode button more than 2 seconds or turning off the power enable to exit loop test...

Страница 11: ...ble unit Set Set Hold down Mode button for 4 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down 1 1 0 30 5 000 5 00...

Страница 12: ...to user s unit setting display A unit can be created by using any characters Up to 13 characters available 1 Up and Down button enables to move on selected characters Set button enables to select a ch...

Страница 13: ...wn Mode button for 6 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down 1 1 4 0 1 60 OFF RESET Lock Unlock Advanced Mode Parame...

Страница 14: ...Adjust brightness of display It is available to set the range between 1 darkest 4 brightest Initial value 4 92 Display timeout Set the time to off the display when there is no operation within a certa...

Страница 15: ...de button for 8 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Disable Enable 2 32 5 00...

Страница 16: ...een 5 to 105 for both X and Y For X it is required to set in ascending order from X001 Be sure that if it is set with other than ascending order cor rect conversion is not carried out Initial value X0...

Страница 17: ...rror occurs only high priority error is displayed Order of priority is EEPROM ERROR OVER RANGE SCALING ERROR in descending order ERROR MESSAGES DISPLAY SETTING INPUT ENGINEERING UNIT VALUE INPUT SCALI...

Страница 18: ...ed in the users manual of the M2ECFG configurator software Or follow the procedure shown below INPUT FINE ADJUSTMENT Set the input signal to 0 and adjust the input to 0 by 06 Angle offset OUTPUT FINE...

Отзывы: