EM-5137-B Rev.1  P. 12 / 18

[60] Unit (INP Scaling)

Set the unit to display input scaling.
Available units are following 68 types.
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W, kW, var, kvar, 
Mvar, VA, Hz, Ω, kΩ, MΩ, cm, mm, m, m/sec, mm/min,  
cm/min, m/min, m/h, m/s

2

, inch, L, L/s, L/min, L/h, m

3

,  

m

3

/sec, m

3

/min, m

3

/h, Nm

3

/h, N∙m, N/m

2

, g, kg, kg/h, N, kN, 

Pa, kPa, Mpa, t, t/h, °C, °F, K, %RH, J, kJ, MJ, rpm, sec, min, 
min

-1

, pH, %, ppm, deg, (blank), User

Selecting ‘User’ enables to move on to user’s unit setting 
display.  A unit can be created by using any characters.  Up 
to 13 characters available.

*1

  Up and Down button enables 

to move on selected characters.  Set button enables to select 
a character.  While setting, pressing Mode button enables to 
delete a character, pressing and holding Mode button ena-
bles to discard the settings.  Pressing and holding Set but-
ton enables to determine the setting and return to setting 
display of [60] Unit (INP Scaling).  The unit is indicated by 
‘INPUT (Scaling)’ at measuring mode display.
If turning power off while setting, it returns to setting 
display of [60] Unit (INP Scaling). (The setting value is 
discarded.)
*1. Settable characters 

0 − 9  A − Z  a − z  ! 

 # $ % &

 ’ ( ) = - + 

*

 ^ 

| @ ` [ ] { } ; : < > ? _ , . /

Initial value: %

[61] Unit (OUT Scaling)

Set the unit to display output scaling.
Available units are following 68 types.
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W, kW, var, kvar, 
Mvar, VA, Hz, Ω, kΩ, MΩ, cm, mm, m, m/sec, mm/min,  
cm/min, m/min, m/h, m/s

2

, inch, L, L/s, L/min, L/h, m

3

,  

m

3

/sec, m

3

/min, m

3

/h, Nm

3

/h, N∙m, N/m

2

, g, kg, kg/h, N, kN, 

Pa, kPa, Mpa, t, t/h, °C, °F, K, %RH, J, kJ, MJ, rpm, sec, min, 
min

-1

, pH, %, ppm, deg, (blank), User

Selecting ‘User’ enables to move on to user’s unit setting 
display.  A unit can be created by using any characters.  Up 
to 13 characters available.

*1

  Up and Down button enables 

to move on selected characters.  Set button enables to select 
a character.  While setting, pressing Mode button enables to 
delete a character, pressing and holding Mode button ena-
bles to discard the settings.  Pressing and holding Set but-
ton enables to determine the setting and return to setting 
display of [61] Unit (OUT Scaling).  The unit is indicated by 
‘OUTPUT (Scaling)’ at measuring mode display.
If turning power off while setting, it returns to setting 
display of [61] Unit (OUT Scaling). (The setting value is 
discarded.)
*1.  Settable characters 

0 − 9  A − Z  a − z  ! 

 # $ % &

 ’ ( ) = - + 

*

 ^ 

| @ ` [ ] { } ; : < > ? _ , . /

Initial value: %

[67] Filter time constant

Set filter time constant of the first order lag filter.
The first order lag filter is available with setting time.  
When ‘0’ is set to this parameter, the first order lag filter is 
not available. (Response time: ≤ 0.5 sec. (0 

 90 %))

The first order lag filter is equivalent to general CR filter.  
The setting time constant is the time to follow until about 
63 %, when input varies from 0 % to 100 %.
It is available to set the range between 0 – 30 seconds.
Initial value: 0

[71] Output Zero fine adjust

Perform fine adjustment of output signal.  Available range 
between −5.000 – +5.000 %.
Initial value: 0.000

[72] Output Span fine adjust

Perform fine adjustment of output signal.  Available range 
between 95.000 – 105.000 %.
Initial value: 100.000

[01] Lockout setting

Set Lock / Unlock of lockout setting.

SETTING VALUE DESCRIPTION

INITIAL VALUE

Lock

Lockout setting enable

Lock

Unlock

Lockout setting disable

Even when setting is ‘Lock’, it is available to move on to 
each setting mode and confirm the setting value of each 
setting parameter. In each setting parameter display, when 
‘Lock’, ‘DATA (Locked)’ is indicated, when ‘Unlock’, ‘DATA’ 
is indicated.

Содержание M2EXS

Страница 1: ...f this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity...

Страница 2: ...ving the socket push down the DIN rail adaptor utilizing a minus screwdriver and pull WALL MOUNTING Refer to the drawings in the shown below TERMINAL CONNECTIONS Connect the unit as in the diagram bel...

Страница 3: ...ing changeable state used to enter save the setting value Used to move on through digits of setting value for input output scaling at setting changeable state Up Button Used to shift through setting p...

Страница 4: ...tting of the Advanced mode for settings DISPLAY IN EACH SETTING MODE For each setting current values of setting parameter ITEM number and setting value are indicated During setting Setting is indicate...

Страница 5: ...RT POWER ON Measuring Mode Hold down Mode Button for 2 seconds Hold down Mode Button for 2 seconds Basic Setting Mode Option Mode Advanced Mode Hold down Mode Button for 2 seconds Hold down Mode Butto...

Страница 6: ...ing value to set value Keeping pressing Down button enables to decrease the value continuously Operation of input setting parameter 06 Angle offset is set by teach The present input value is displayed...

Страница 7: ...ds Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Do...

Страница 8: ...input scaling 99999 999999 100 00 16 Input decimal point No decimal point The number of decimal places 1 5 2 places of decimals 17 Output range 0 20mA 5 5V 10 10V 0 20mA 18 0 output setting 0 000 19 0...

Страница 9: ...the unit SETTING VALUE DESCRIPTION INITIAL VALUE 0 20 mA Output 0 20 mA DC 0 20 mA 5 5 V Output 5 5 V DC 10 10 V Output 10 10 V DC When output range is changed turn the power off and then set the outp...

Страница 10: ...ase it by pressing Up and Down button Press and hold them enables to change value continuously 1 Pressing and holding Mode button more than 2 seconds or turning off the power enable to exit loop test...

Страница 11: ...ble unit Set Set Hold down Mode button for 4 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down 1 1 0 30 5 000 5 00...

Страница 12: ...to user s unit setting display A unit can be created by using any characters Up to 13 characters available 1 Up and Down button enables to move on selected characters Set button enables to select a ch...

Страница 13: ...wn Mode button for 6 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down 1 1 4 0 1 60 OFF RESET Lock Unlock Advanced Mode Parame...

Страница 14: ...Adjust brightness of display It is available to set the range between 1 darkest 4 brightest Initial value 4 92 Display timeout Set the time to off the display when there is no operation within a certa...

Страница 15: ...de button for 8 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Disable Enable 2 32 5 00...

Страница 16: ...een 5 to 105 for both X and Y For X it is required to set in ascending order from X001 Be sure that if it is set with other than ascending order cor rect conversion is not carried out Initial value X0...

Страница 17: ...rror occurs only high priority error is displayed Order of priority is EEPROM ERROR OVER RANGE SCALING ERROR in descending order ERROR MESSAGES DISPLAY SETTING INPUT ENGINEERING UNIT VALUE INPUT SCALI...

Страница 18: ...ed in the users manual of the M2ECFG configurator software Or follow the procedure shown below INPUT FINE ADJUSTMENT Set the input signal to 0 and adjust the input to 0 by 06 Angle offset OUTPUT FINE...

Отзывы: