EM-5135-B Rev.5 P. 4 / 19
EXTERNAL VIEWS
Display
Mode Button
Set Button
Configurator Jack
Up Button
Down Button
Up
Down
Mode
Set
Output Setting DIP SW
ON
1
2
3
4
5
6
7
8
SW1
OFF
ON
1
2
3
4
5
6
7
8
SW1
OFF
PERCENT
100.00
OUTPUT
20.000
%
mA
COMPONENT
FUNCTION
Display
Indicates present values, setting values and abnormal information.
Two types of present values are displayed respectively at the upper and lower parts according to setting.
Mode Button
Shifts from Measuring mode to each setting mode.
The destination changes depending on how long the button is held down.
Pressing Mode button for ≥ 2 seconds returns to Measuring mode from each setting mode..
Set Button
Shifts the setting value of each setting parameter item to a setting changeable state.
When at setting changeable state, used to move through the digits of setting value for input/output scal-
ing and to enter (save) the setting value.
Up Button
Shifts through setting parameter items and to increase or select the setting value.
Down Button
Shifts through setting parameter items and to decrease or select the setting value.
Configurator Jack
Used to perform configuration with M2E configurator software (model: M2ECFG).
When using the software, set the Lockout setting of the unit to ‘Lock’.
DIP SWITCH
The internal DIP switch for output setting is required to select output types before setting a precise output range using front
buttons or setting with a PC.
Refer to the “PROGRAMMING” for the operation with front buttons. Refer to the users manual (EM-5147) of M2E Configura-
tor Software (model: M2ECFG) for setting with PC.
Output Range
SW1
1
2
3
4
5
6
7
8
0 – 20 mA
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
-5 – +5 V
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
-10 – +10 V
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
CAUTION:
DO NOT set DIP switches while power is supplied. Otherwise, the unit may fail.