background image

M2EXM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5135-B  Rev.5  P. 4 / 19

EXTERNAL VIEWS

Display

Mode Button

Set Button

Configurator Jack

Up Button

Down Button

Up

Down

Mode

Set

Output Setting DIP SW

ON

1

2

3

4

5

6

7

8

SW1

OFF

ON

1

2

3

4

5

6

7

8

SW1

OFF

PERCENT

100.00

OUTPUT

20.000

%

mA

COMPONENT

FUNCTION

Display

Indicates present values, setting values and abnormal information.  
Two types of present values are displayed respectively at the upper and lower parts according to setting.

Mode Button

Shifts from Measuring mode to each setting mode.  
The destination changes depending on how long the button is held down.
Pressing Mode button for ≥ 2 seconds returns to Measuring mode from each setting mode..

Set Button

Shifts the setting value of each setting parameter item to a setting changeable state.
When at setting changeable state, used to move through the digits of setting value for input/output scal-
ing and to enter (save) the setting value.

Up Button

Shifts through setting parameter items and to increase or select the setting value.

Down Button

Shifts through setting parameter items and to decrease or select the setting value.

Configurator Jack

Used to perform configuration with M2E configurator software (model: M2ECFG).  
When using the software, set the Lockout setting of the unit to ‘Lock’.

DIP SWITCH

The internal DIP switch for output setting is required to select output types before setting a precise output range using front 
buttons or setting with a PC.
Refer to the “PROGRAMMING” for the operation with front buttons.  Refer to the users manual (EM-5147) of M2E Configura-
tor Software (model: M2ECFG) for setting with PC.

Output Range

SW1

1

2

3

4

5

6

7

8

0 – 20 mA

OFF

ON

OFF

OFF

OFF

OFF

ON

OFF

-5 – +5 V

OFF

OFF

ON

OFF

ON

OFF

OFF

ON

-10 – +10 V

OFF

OFF

ON

OFF

OFF

ON

OFF

ON

 

CAUTION:

 DO NOT set DIP switches while power is supplied.  Otherwise, the unit may fail.

Содержание M2EXM

Страница 1: ...9 OPERATING MANUAL Mini M POTENTIOMETER TRANSMITTER PC programmable MODEL M2EXM CONTENTS BEFORE USE 2 POINTS OF CAUTION 2 COMPONENT IDENTIFICATION 2 INSTALLATION 3 TERMINAL CONNECTIONS 3 EXTERNAL VIEWS 4 DIP SWITCH 4 SCREEN DISPLAY 5 PROGRAMMING 6 ERROR MESSAGES 18 WIRING INSTRUCTIONS 18 CHECKING 18 MAINTENANCE 19 LIGHTNING SURGE PROTECTION 19 ...

Страница 2: ...rements in regard to the whole system and employ additional protective measures to ensure the CE conform ity Install lightning surge protectors for those wires connect ed to remote locations POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V AC rating 85 264V 47 66 Hz 4 5VA at 100V AC 6 5VA at 200V ...

Страница 3: ... RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of base socket on the DIN rail and push in the lower When removing the socket push down the DIN rail adaptor utilizing a minus screwdriver and pull WALL MOUNTING Refer to EXTERNAL DIMENSIONS TERMINAL CONNECTIONS Connect the unit as in the diagram below or refer to the connectio...

Страница 4: ...geable state When at setting changeable state used to move through the digits of setting value for input output scal ing and to enter save the setting value Up Button Shifts through setting parameter items and to increase or select the setting value Down Button Shifts through setting parameter items and to decrease or select the setting value Configurator Jack Used to perform configuration with M2...

Страница 5: ...ed mode for details DISPLAY IN EACH SETTING MODE In each setting mode setting parameter item name item No and setting value are indicated During setting Setting is indicated next to DATA If the power is mistakenly shut down during setting the set value is discarded and returns to the value before setting change Setting display previously displayed before power shut down is indicated at next power ...

Страница 6: ...ART POWER ON Measuring Mode Hold down Mode Button for 2 seconds Hold down Mode Button for 2 seconds Basic Setting Mode Option Mode Advanced Mode Hold down Mode Button for 2 seconds Hold down Mode Button for 4 seconds Hold down Mode Button for 2 seconds Hold down Mode Button for 6 seconds Linearization Mode Hold down Mode Button for 2 seconds Hold down Mode Button for 8 seconds ...

Страница 7: ...to set value Keeping pressing Down button enables to decrease the value continuously Note DO NOT press 2 or more buttons simultaneously Operation of input setting parameter 12 0 input setting 13 100 input setting are set by teach The present input value is displayed by pressing set button With input value desired as 0 and 100 is entered pressing set button again enables to fix the setting Input ou...

Страница 8: ...Loop test Set Set Hold down Mode button for 2 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Lock Unlock 100 Teach 0 Teach 99999 999999 99999 999999 oooooo ooooo o oooo oo ooo ooo oo oooo o ooooo 0 2...

Страница 9: ...9999 0 00 15 100 input scaling 99999 999999 100 00 16 Input decimal point No decimal point The number of decimal places 1 5 2 places of decimals 17 Output range 0 20 mA 5 5 V 10 10 V 0 20 mA 18 0 output setting 0 000 19 000 5 000 4 750 10 000 9 000 mA V V 4 000 19 100 output setting 1 000 20 000 4 750 5 000 9 000 10 000 mA V V 20 000 20 0 output scaling 99999 999999 0 00 21 100 output scaling 9999...

Страница 10: ... 2 places of decimals ooooo o Number of decimal places 1 oooo oo Number of decimal places 2 ooo ooo Number of decimal places 3 oo oooo Number of decimal places 4 o ooooo Number of decimal places 5 17 Output range Set the range of output signal of the unit SETTING VALUE DESCRIPTION INITIAL VALUE 0 20 mA Output 0 20 mA DC 0 20 mA 5 5 V Output 5 5 V DC 10 10 V Output 10 10 V DC When output range is c...

Страница 11: ...ease it by pressing Up and Down button Press and hold them enables to change value continuously 1 Pressing and holding Mode button more than 2 seconds or turning off the power enable to exit loop test ITEM 26 Loop test ITEM 26 DATA Setting DATA Setting Loop test Loop test Up Down button Set button Set mA 4 000 0 00 Cancel Output engineering value Output value 1 While loop test is performing actual...

Страница 12: ... Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down 1 1 0 30 5 000 5 000 95 000 105 000 5 000 5 000 95 000 105 000 Lock Unlock Option Mode Parameters MODE ITEM SETTING PARAMETER RANGE UNIT INITIAL VALUE Option 60 Unit INP Scaling Choose from 68 types 61 Unit OUT Scaling Choose from 68 types...

Страница 13: ...n button enables to move on selected characters Set button enables to select a character While setting pressing Mode button enables to delete a character pressing and holding Mode button ena bles to discard the settings Pressing and holding Set but ton enables to determine the setting and return to setting display of 61 Unit OUT Scaling The unit is indicated by OUTPUT Scaling at measuring mode dis...

Страница 14: ...own Mode button for 6 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down 1 1 4 0 1 60 OFF RESET Lock Unlock Advanced Mode Parameters MODE ITEM SETTING PARAMETER RANGE UNIT INITIAL VALUE Advanced 90 Display setting Upper choose from 5 types Lower choose from 6 types Upper INPUT Lower PERCENT 91 Brightness 1 darkest 4 brightest...

Страница 15: ...ted by 0 10000 as total resistance is 10000 4 Display the value converted as 0 00 to 100 00 based on input setting value 91 Brightness Adjust brightness of display It is available to set the range between 1 darkest 4 brightest Initial value 4 92 Display timeout Set the time to off the display when there is no operation within a certain time It is available to set the range between 0 60 minutes Set...

Страница 16: ...de button for 8 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Disable Enable 2 111 5 00 105 00 5 00 105 00 5 00 105 00 5 00 105 00 Lock Unlock Linearization Mode Parameters MODE ITEM SETTING PARAMETER RANGE UNIT INITIAL VALUE Linearization 100 User s table linearization Disable Enable ...

Страница 17: ...vailable between 5 to 105 for both X and Y For X it is required to set in ascending order from X001 Be sure that if it is set with other than ascending order cor rect conversion is not carried out Initial value X001 5 00 Y001 5 00 X002 105 00 Y002 105 00 E g X001 105 105 5 Y005 Input Output Y004 Y003 Y002 Y001 5 X003 X002 X004 X005 When the input is not defined in the user s table two near est val...

Страница 18: ...follows depending on setting value of display setting Error is indicated blinking at upper or lower When multiple error occurs only high priority error is displayed Order of priority is EEPROM ERROR OVER RANGE SCALING ERROR in descending order ERROR MESSAGES DISPLAY SETTING INPUT ENGINEERING UNIT VALUE INPUT SCALING VALUE PERCENT VALUE OUTPUT ENGINEERING UNIT VALUE OUTPUT SCALING VALUE OVER RANGE ...

Страница 19: ...al EM 5147 when adjusting with M2E Configurator Software model M2ECFG And then follow the procedure shown below INPUT FINE ADJUSTMENT 1 Set the input signal to 0 and adjust the input display to 0 by 69 Input Zero fine adjust 2 Set the input signal to 100 and adjust the input display to 100 by 70 Input Span fine adjust 3 Again set the simulated input to 0 confirm the input display 4 If input displa...

Отзывы: