M2EXM
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5135-B Rev.5 P. 11 / 19
[26] Loop test
As pressing Set button enables to blink ‘Cancel’, changing to ‘Set’ by pressing Up or Down and pressing ‘Set’ allows to indicate
Loop Test display.
Present value is indicated. Increase or decrease it by pressing Up and Down button. Press and hold them enables to change
value continuously.*
1
Pressing and holding Mode button more than 2 seconds or turning off the power enable to exit loop test.
ITEM
26
Loop test
ITEM
26
DATA (Setting)
DATA (Setting)
Loop test
Loop test
Up/Down
button
Set button
Set
mA
4.000
0.00
%
Cancel
Output engineering value
Output % value
*1. While loop test is performing, actual input is disregarded.
While loop test is performing and ‘Display timeout’ is enabled to display off, return to the display on by pressing a front button.