ALARM SETTING
RGTR.
PARAMETER
UNIT
6369
Power ON delay time
0 to 999 : Seconds
Factory setting : 0
Seconds
6370
Latching
0 : No latching (*)
1 : Latching (Alarm trip is held until a reset command is received or power OFF)
----
6371
I1 thr. I3 - Current : High setpoint
Factory setting : 0
mA
6373
I1 thr. I3 - Current : Low setpoint
Factory setting : 0
mA
6375
I1 thr. I3 - Current : Alarm output
0 : Disable (*)
1 : Display only
2 : D discrete output 1
3 : D discrete output 2
----
6376
I1 thr. I3 - Current : Hysteresis (deadband)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
%/10
6377
I1 thr. I3 - Current : ON delay time
0 to 999 : Seconds
Factory setting : 0
Seconds
6379
IN - Neutral current : High setpoint
3P4W
3.00
Factory setting : 0
mA
6381
IN - Neutral current : Low setpoint
3P4W
3.00
Factory setting : 0
mA
6383
IN - Neutral current : Alarm output
3P4W
3.00
0 : Disable (*)
1 : Display only
2 : D discrete output 1
3 : D discrete output 2
----
6384
IN - Neutral current : Hysteresis (deadband)
3P4W
3.00
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
%/10
6385
IN - Neutral current : ON delay time
3P4W
3.00
0 to 999 : Seconds
Factory setting : 0
Seconds
6387
U12 thr. U31 - Delta voltage : High setpoint
Factory setting : 0
V/100
6389
U12 thr. U31 - Delta voltage : Low setpoint
Factory setting : 0
V/100
6391
U12 thr. U31 - Delta voltage : Alarm output
0 : Disable (*)
1 : Display only
2 : D discrete output 1
3 : D discrete output 2
----
6392
U12 thr. U31 - Delta voltage : Hysteresis (deadband)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
%/10
6393
U12 thr. U31 - Delta voltage : ON delay time
0 to 999 : Seconds
Factory setting : 0
Seconds
6395
U1N thr. U3N - Phase voltage : High setpoint
Factory setting : 0
V/100
6397
U1N thr. U3N - Phase voltage : Low setpoint
Factory setting : 0
V/100
6399
U1N thr. U3N - Phase voltage : Alarm output
0 : Disable (*)
1 : Display only
2 : D discrete output 1
3 : D discrete output 2
----
6400
U1N thr. U3N - Phase voltage : Hysteresis (deadband)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
%/10
6401
U1N thr. U3N - Phase voltage : ON delay time
0 to 999 : Seconds
Factory setting : 0
Seconds