54UC
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6489-B Rev.9 P. 12 / 47
CC-Link - SETTING
■
SYSTEM OPERATIONS
RGTR.
PARAMETER
UNIT
5601
System configuration
0 : Single-phase / 2-wire (1CT)
1 : Single-phase / 3-wire (2CT)
2 : 3-phase / 3-wire, balanced load (1CT)
3 : 3-phase / 3-wire, unbalanced load (2CT) (*)
4 : 3-phase / 4-wire, balanced load (1CT)
3P4W
5 : 3-phase / 4-wire, unbalanced load (3CT)
3P4W
6 : 3-phase / 3-wire, unbalanced load (3CT)
3P4W
5602
CT rating, Primary
1 to 20 000 : Current (A)
Factory setting : 1 or 5
A
5603
CT rating, Secondary
1 to 5
Factory setting : 1 or 5
A
5604
VT rating, Primary
50 to 400 000 : Voltage (V)
Factory setting : 110
V
5606
VT rating, Secondary
50 to 500 : Voltage (V)
Factory setting : 110
V
5607
Frequency input
0 : Voltage (*)
1 : Current
----
5608
Low-end cutout, Current
0 to 999 : Rated current × 0.001 × Specified value
Factory setting : 10
%/10
5609
Low-end cutout, Voltage
0 to 999 : Rated voltage × 0.001 × Specified value
Factory setting : 10
%/10
(*) Factory setting
■
DEMAND SETTING
RGTR.
WORD
PARAMETER
UNIT
5857
1
Average (demand) current update interval
0 : External trigger signal
1 to 60 : Minutes
Factory setting : 30
Minutes
5858
1
Average (demand) power update interval
0 : External trigger signal
1 to 60 : Minutes
Factory setting : 30
Minutes